Use the DC terminals on the flame safety to read the pilot flame signal
Record the pilot flame signal in the Start-Up Sheet
Record the low and high fire flame signal on the Start-Up Sheet
Setting High Fire
Open the Burner Gas Shut Off Valve
Measure the intake air temperature.
Add the intake air temperature to the units nameplate design temperature rise.
This result will be the desired high fire discharge temperature.
Example: Intake Temp 70 F
Design Temp Rise
72 F
Discharge Temp
142 F
PILOT REGULATOR
OPEN VALVE
GAS TYPE: NATURAL
MAX. TEMP. RISE: 140 F
DESIGN TEMP. RISE: 72 F
MAX. DISCHARGE TEMP.: 80
F
POSITIVE TERMINAL
NEGATIVE TERMINAL
+
-