Check that all terminal screws are tight and that wires are in place
Check pulley alignment. Correct if necessary
Check that the power supply matches the nameplate
voltage, phase, and amperage
Record the voltage on the Start-Up Sheet
Check that the gas type and pressure matches the
nameplate type and pressure
Check that the gas type and pressure matches the
nameplate type and pressure
Contact the service department is the power or gas
supply needs to be changed in the field. Different parts
might be necessary for the change
Turn the remote panel switch to OFF if blower and burner
service switches were supplied
Set the temperature set point dial to the maximum
Turn the main power disconnect ON
Bump the blower motor starter to check the blower
wheel rotation
The decal is located on the blower housing
If the rotation is backwards turn off the power and
correct the wiring
The rotation can be corrected by interchanging two
legs of 3 phase (must be between vfd and motor on vav units)
ROTATION