Rigging – FloAire FAV User Manual

Page 5

background image

5

7. Situate the unit above ground or at roof level

high enough to prevent precipitation from
being drawn into its inlet.

8. The inlet must also be located at least 10

feet away from any exhaust vents.

9. The heater inlet must be located in

accordance with the applicable building
code provisions for ventilation air.

10. All air to the heater must be ducted from the

outdoors.

11. Recirculation of room air is not permitted. If

in doubt regarding the application, consult
the manufacturer.

12. The unit must have adequate structural

support or the equipment or building could
be damaged.

13. Do not alter or otherwise restrict combustion

or ventilation openings.

14. Direct-fired units should not be installed

downstream from cooling systems which
use refrigerants for cooling.


COMBUSTABLE

CLEARANCES

The top, back, and front surfaces

of this heater may not be installed

less than 6 inches from

combustible materials. The heater

base may be installed on

combustible surfaces.


SERVICE CLEARANCES

Allow 24 inches or greater

minimum service clearance on all

sides of this heater. Allow 48

inches or greater on the vestibule

and blower door side.




Rigging

1. Horizontal units are supplied with four lifting lugs on the bottom corners of the casing.
2. Vertical units are supplied with four lifting lugs at the top corners of the casings.
3. Lift the unit and accessories separately, attach the accessories to the unit once the unit is in place.
4. The following diagrams represent the proper methods for lifting the unit and accessories.
5. Always use spreader bars to prevent damage to the unit casing.