Remote panel troubleshooting chart – FloAire FAV User Manual
Page 28
28
Remote Panel Troubleshooting Chart
Light Indication
Condition
Possible Cause
No lights
Power not available to Remote Panel
Bad voltage to unit
Main Disconnect in “OFF” position
Circuit breaker tripped
Bad main transformer
POWER light only
Proper unit Off Operation
No problem
No power to motor starter
Manual/Off/Auto switch in “OFF”
position (3-position Remote Panels
only)
Improper damper function
Low Temperature Thermostat timed out
(option)
POWER light and
BLOWER ON light
Proper ventilation operation
No problem
No power to flame safety controller
Manual/Off/Auto switch in “OFF”
position (2-position Remote Panels
only)
Heat/Vent switch in “VENT” position
Gas pressure switch Tripped (option)
High Temperature Limit Thermostat
tripped
Manual/Off/Auto Switch in “AUTO”
position and Intake Air Thermostat not
satisfied
Improper airflow
Insufficient airflow
Excessive airflow
Bad airflow switch
Problem with air probes
Problem with airflow tubing
Broken belt
POWER light and
BLOWER ON light and
BURNER ON light
Proper heating operation
No problem
CLOGGED FILTER light on
(optional)
Filters clogged
Filters dirty or need replacement
FLAME FAILURE light on
Flame safety alarm activated
No flame detected during pilot
establishment period
Combination valve in “OFF” position
(Unit sizes 1-3)
Stuck closed gas valve
No or low gas pressure
Bad spark electrode
Bad ignition transformer
Flames sensor malfunction
Clogged pilot orifices