GB - 8

38VYX050/38VYX080

• When there is a possibility of freezing of drain at the cold district

or a snowfall area, be careful for drainage ability of drain.
The drainage ability increases when a knockout hole on the base
plate is opened. (Open the knockout hole to outside using a
screwdriver, etc.)

Table VII: Piping connection

Capacity rank

Liquid piping

Gas piping

Outer diameter

Thickness

Outer diameter

Thickness

38 VYX 050

ш 6,4

0,8

ш 12,7

0,8

38 VYX 080

ш 9,52

0,8

ш 15,87

1,0

• In case of draining through the drain hose, attach the following

drain nipple and the waterproof rubber cap, and use the drain
hose (Inner diam.: 16mm) sold on the market.
And also seal the screws securely with silicone material, etc. so
that water does not drop down. Some conditions may cause
dewing or dripping of water.

Drain nipple

Table VI: Optional Installation Parts

(local procure)

CAUTION:
IMPORTANT FOR POINTS BELOW FOR PIPING WORK

1. Keep dust and moisture away from inside the connecting

pipes.

2. Tightly connect the connection between pipes and the unit.
3. Evacuate the air in the connecting pipes using VACUUM

PUMP.

4. Check gas leak at connected points.

Installation

Waterproof rubber cap

Knockout hole

Waterproof rubber cap

Drain nipple

A Open

38 VYX 080

Parts name

Q’ty

Refrigerant piping

A

Liquid side: ø 6,35 mm o ø 9,52 mm

Each one

Gas side: ø 12,7 mm o ø 15,9 mm

B

Pipe insulating material

1

(polyethylene foam, 6 mm thick)

C

Putty, PVC tapes

Each one

A

Waterproof rubber
cap

Base plate

Drain nipple