38VYX050/38VYX080

GB - 10

All field electrical connections are the responsibility of the
installer.

WARNING:
• Wrong wiring may cause a burn-out to some electrical parts.
• Be sure to use the cord clamps attached to the product.
• Do not damage or scratch the conductive core and inner insulator

of power and inter-connecting cables when peeling them.

• Be sure to comply with local regulations of the cable from outdoor

unit to indoor unit.
(wire size and cabling method etc.)

• Use the power and Inter-connecting cables with specified

thickness, specified type and protective devices required.

38VYX050
How to remove the cover

1. Remove screws of the valve cover.
2. Pull the valve cover downward to remove it.

1. Connect the connecting cable to the terminal as identified with

their respective numbers on the terminal block of indoor and
outdoor unit.

Evacuating

• Open the valve stem or the handle until it strikes the stopper.

It is unnecessary to apply further force.

• Securely tighten the cap with a torque wrench.

• Cap tightening torque

ø 6,35

14 a 18 N•m (1,4 a 1,8 kgf•m)

Valve

ø 9,52

33 a 42 N•m (3,3 a 4,2 kgf•m)

size

ø 12,70

33 a 42 N•m (3,3 a 4,2 kgf•m)

ø 15,87

20 a 25 N•m (2,0 a 2,5 kgf•m)

Service connection

14 a 18 N•m (1,4 a 1,8 kgf•m)

Electrical connections

• Make refrigerant connections before electrical

connections.
When disconnecting, disconnect electrical connections before
refrigerant connections.

IMPORTANT:
Make ground connection prior to any other electrical
connections.

Power cable and connecting cable

• The installation fuse (25A D type

) must be used for the

power supply line of this air conditioner.

• Incorrect/incomplete wiring might cause an electrical fire or

smoke.

• Prepare the exclusive power supply for the air conditioner.

• Ensure that mains supply connection is made through a switch

that disconnects all poles, with contact gap of a least 3 mm.

• The indoor - outdoor unit interconnecting wires must be A07 RN-F

type (245 IEC 57) or higher, with synthetic rubber insulation with
Neoprene coating, according to EN 60335-2-40 codes.

• The mains supply connecting cable for 38VYX units, must be H07

RN-F type (245 IEC 57) or higher, with synthetic rubber insulation
with Neoprene coating, according to EN 60335-2-40 codes.
Refer to the indoor unit installation manual for sizing of the
power supply wires.

2. For inter connecting cable, do not use a wire jointed to another

on the way.
Use wires long enough to cover the entire length.

Connecting
cable

Power cable

Ground
connector

(mm)

10

30

1 2 3

10

10

L N

30

40

Valve handling precautions

Connecting

cable

Power cable

1 2 3 L N

Terminal block

Piping cover

Cord clamp

Indoor/outdoor

connecting cables

Power cable

Valve cover

Model

38VYX050

38VYX080

Power supply

220

÷

240 V

Single phase

50 Hz

Maximum running current

12 A

15A

Installation

25 A (type D

)

fuse rating

Power cable

H07 RN-F (245 IEC 57)

2,5 mm

2