A. all air from inside buildings, Installation instructions (cont’d) – Kenmore 153.335963 User Manual
Page 12
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
Installation Instructions (cont’d)
Combustion Air and Ventilation
for Appliances Located in
Unconfined Spaces
Unconfîned Space
is a space whose volume is not less than 50 cubic
feet per
1,000
Bcu per hour of the aggregate input rating of all appli
ances installed in that space. Rooms communicating directly with the
space in which the appliances are installed, through openings not fur
nished with doors, are considered a part of the unconfined space.
In unconfined spaces in buildings, infiltration may be adequate to
provide air for combustion, ventilation and dilution of flue gases.
However,
in
buildings
of
tight
construction
(for
example,
weather
stripping, heavily insulated, caulked, vapor barrier, etc.), additional air
may need to be provided using the methods described in Combustion
Air and Ventilation for Appliances Located in Confined Spaces.
Combustion Air and Ventilation
for Appliances Located in
Confined Spaces
Confined Space
is a space whose volume is less than
50
cubic feet per
1,000
Btu per hour of the aggregate input rating of all appliances
installed in that space.
a. ALL AIR FROM INSIDE BUILDINGS:
(See Page 9 Figure 1, and Figure
6
below)
The confined space shall be provided with two permanent open
ings communicating directly with an additional room(s) of suffi
cient volume so that the combined volume of all spaces meets the
criteria for an unconfined space. The total input of all gas utiliza
tion equipment installed in the combined space shall be considered
in making this determination. Each opening shall have a minimum
free area of one square inch per 1,000 BTU per hour of the total
input rating of all gas utilization equipment in the confined space,
but not less than 100 square inches. One opening shall commence
within
12
inches of the top and one commencing within
12
inches
of the bottom of the enclosure.
Figure 6
b. ALL AIR FROM OUTDOORS:
(see Figures 7-9)
The confined space shall be provided with two permanent open
ings, one commencing within
12
inches of the top and one com
mencing
within
12
inches
from
the
bottom
of
the
enclosure.
The openings shall communicate directly, or by ducts, with the
outdoors or spaces (crawl or attic) that freely communicate with
the outdoors.
Figure 7
1. When directly communicating with the outdoors, each opening
shall have a minimum free area of
1
square inch per 4,000 BTU
per hour of total input rating of all equipment in the enclosure.
(Sec Figure 7.)
2.
When communicating with the outdoors through vertical ducts,
each opening shall have a minimum free area of
1
square inch
per 4,000 BTU per hour of total input rating of all equipment in
the enclosure. (See Figure
8
.)
Figure 8
3.
When
communicating
with
the
outdoors
through
horizontal
ducts, each opening shall have a minimum free area of
1
square
inch per 2,000 BTU per hour of total input rating of all equip
ment in the enclosure. (See Figure 9.)
4. When ducts are used, they shall be of the same cross-sectional area
as the free area of the openings to which they connect. The mini
mum short side dimension of rectangular air ducts shall not be
less than 3 inches. (See Figure 9.)
5.
Louvers and Grilles: In calculating free area, consideration shall be
given to the blocking effect of louvers, grilles or screens protect
ing openings. Screens used shall not be smaller than !4 inch mesh.
If the free area through a design of louver or grille is known, it
should be used in calculating the size opening required to provide
the free area specified. If the design and free area is not known, it
may be assumed that wood louvers will be 20-25 percent free area
and metal louvers and grilles will have 60-75 percent free area.
Louvers and grilles shall be fixed in the open position or inter
locked with the equipment so that they are opened automatically
during equipment operation.
6
.
Special
Conditions
Created
by
Mechanical
Exhausting
or
Fireplaces; Operation of exhaust fans, ventilation systems, clothes
dryers or fireplaces may create conditions requiring special atten
tion to avoid unsatisfactory operation of installed gas utilization
equipment.
12