Caution, Start up conditions, Thermal expansion tank specifications – Kenmore 153.33443 User Manual
Page 23: Expansion tank sizing chart, Thermal expansion, Property damage hazard, Draft hood operation
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
start Up Conditions
Thermal Expansion
CAUTION
Property Damage Hazard
■
Avoid water heater damage,
■
Install thermal expansion tank or device if necessary.
' Contact qualified installer or service agency.
Water supply system may, because of such events as high line
pressure, frequent cut-offs, and the effects of water hammer
have installed devices such as pressure reducing valves, check
valves, back flow preventers, etc., to control these types of
problems. When these devices are not equipped with an internal
by-pass, and no other measures are taken, the devices cause
the water system to be closed. As water Is heated, it expands
(thermal expansion) and closed systems do not allow for the
expansion of heated water.
The water within the water heater tank expands as it is heated
and increases the pressure of the water system. If the relieving
point
of
water
heater's
temperature-pressure
relief
valve
is
reached,
the
valve
will
relief
the
excess
pressure.
The
temperature-pressure
relief
valve
is
not
intended
for
the
constant
relief of thermal expansion.
This is an unacceptable
condition and must be corrected.
It is recommended that any devices installed which could create
a closed system have a by-pass and/or the system have an
expansion tank or device to relieve the pressure built by thermal
expansion. Thermal expansion tanks are available from Sears
stores and through the Sears Service Centers. Contact the
local
plumbing
inspector,
water
supplier
and/or
the
Sears
Service
Center
for
assistance
in
controlling
these
situations.
See Figure 26.
Thermal Expansion Tank Specifications
Model
Number
Tank
Capacity
In Gallons
Dimensions
in Inches
Pipe
Fitting
On Tank
Diameter
Lenath
153.331020
2
8 1203 mm)
12-3/4 (323 mm)
3/4” Male
153.331050
5
11 (279 mm)
14-3/4 (375 mm)
3/4” Male
Expansion Tank Sizing Chart
Expansion
Tank
Capacity
Needed
inlet*
Water
Pressure
Water Heater Capacity (Gallons)
30
40
50
66
80
40psi
2
2
2
5
5
SOpsi
2
2
2
5
5
60psi
2
2
5
5
5
70psi
2
2
5
5
5
SOpsi
2
5
5
5
5
NOTE:
Expansion
tanks
are
pre-charged
with
a
40
psi
air
charge. If the
inlet water
pressure is higher than 40 psi, the
expansion
tank’s
air
pressure
must
be
adjusted
to
match
that pressure,
but
must not be higher than 80 psi.
WATER
HEATER
(3}
‘Highest recorded inlet water pressure in a 24 hour period or
regulated water pressure.
Possible noises due to expansion and contraction of some metal
parts during periods of heat-up and cool-down do not represent
harmful or dangerous conditions.
Condensation causes sizzling and popping within the burner
area
during
heating
and
cooling
periods
and
should
be
considered normal. See Condensation section.
Draft Hood Operation
Check
draft
hood
operation
by
performing
a
worst
case
depressurization of the building. With all doors and windows
closed, and with all air handling equipment and exhaust fans
operating such as furnaces, clothes dryers, range hoods and
bathroom fans, a match flame should still be drawn into the
draft hood of the water heater with its burner firing. If the flame
23