Temperature-pressure relief valve, Temperature pressure relief valve -14, Caution – Kenmore 153.33443 User Manual
Page 14: Adanger, Arning, Explosion hazard, Water damage hazard
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
Fit T & P valve insulation over valve. Make sure that the insulation
does not interfere with the lever of the T & P valve.
Secure all insulation using tape.
Temperature-Pressure Relief Valve
▲W
arning
Explosion Hazard
Temperature-pressure relief valve
must comply with ANSI Z2122
and ASME code.
Property
sized
temperature-
pressure relief valve must be
installed in opening provided.
Can result in overheating and
excessive tank pressure
Can cause serious injury or death.
This heater is provided with a properly certified combination
temperature - pressure relief valve by the manufacturer.
The valve is certified by a nationally recognized testing laboratory
that
maintains
periodic
inspection
of
production
of
listed
equipment as meeting the requirements for Relief Valves and
Automatic Gas Shutoff Devices for Hot Water Supply Systems,
ANSI Z21.22 and the code requirements of ASME.
If replaced, the valve must meet the requirements of local
codes,
but
not
less
than
a
combination
temperature
and
pressure
relief
valve
certified
as
indicated
in
the
above
paragraph.
The valve must be marked with a maximum set pressure not
to
exceed
the
marked
hydrostatic
working
pressure
of
the
water heater (150 psi = 1,035 kPa) and a discharge capacity
not less than the water heater input rate as shown on the
model rating plate.
For safe operation of the water heater, the relief valve must not
be removed from its designated opening nor plugged.
The temperature-pressure relief valve must be installed directly
into the fitting of the water heater designed for the relief valve.
Position the valve downward and provide tubing so that any
discharge will exit only within 6 Inches (153 mm) above, or at
any distance below the structural floor, see Figure 16. Be certain
that no contact is made with any live electrical part. The
discharge opening must not be blocked or reduced in size under
any
circumstances.
Excessive
length,
over
30
feet
(9.14 m), or use of more than four elbows can cause restriction
and reduce the discharge capacity of the valve.
No valve or other obstruction is to be placed between the relief
vaive and the tank. Do not connect tubing directly to discharge
drain unless a 6 inch air gap is provided. To prevent bodily
injury, hazard to life, or property damage, the relief valve must
be allowed to discharge water in quantities should circumstances
demand. If the discharge pipe is not connected to a drain or
other
suitable
means,
the
water
flow
may
cause
property
damage.
FIGURE 16.
CAUTION
Water Damage Hazard
■ Temperature-pressure relief valve discharge
pipe must terminate at adequate drain.
•
The Discharge Pipe:
• Shall not be smaller in size than the outlet pipe size of the
valve, or have any reducing couplings or other restrictions.
• Shall not be plugged or blocked.
• Shall be of material listed for hot water distribution.
” Shall be installed so as to allow complete drainage of both
the temperature-pressure relief valve, and the discharge
pipe.
• Shall terminate at an adequate drain.
• Shall not have any valve between the relief valve and tank.
ADANGER
Water
temperature
over
125°F
(52°C)
can
cause
severe
burns
instantly resulting in severe injury
or death.
Children,
the
elderly,
and
the
physically
or
mentally
disabled
are at highest riskfor scald injury.
Feel
water
before
bathing
or
showering.
Temperature
limiting
valves
are
available.
Read instruction manual for safe
temperaturesetting.
14