Caution, Property damage hazard – Kenmore 153.33443 User Manual
Page 13
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
This water heater shall not be connected to any heating systenns
or
component(s)
used
with
a
non-potable
water
heating
appliance.
All piping components connected to this unit for space heating
applications shall be suitable for use with potable water.
Toxic chemicals, such as those used for boiler treatment shall
not be introduced into this system.
Water supply systems may, because of such events as high
line pressure, frequent cut-offs or the effects of water hammer
among others, have installed devices such as pressure reducing
valves, check valves, back flow preventers, etc. to control these
types of problems. When these devices are not equipped with
an interna! by-pass, and no other measures are taken, the
devices cause the water system to be closed. As water Is heated,
it expands (thermal expansion) and closed systems do not allow
for the expansion of heated water.
The water within the water heater tank expands as it is heated
and increases the pressure of the water system.
If
the relieving
point of the water heater's temperature-pressure relief valve Is
reached,
the
valve
will
relieve
the
excess
pressure.
The
temperature-pressure
relief
valve
is
not
intended
for
the
constant relief of thermal expansion.
This is an unacceptable
condition and must be corrected. It is recommended that any
devices installed which could create a closed system have a
by-pass and/or the system have an expansion tank to relieve
the pressure built by thermal expansion in the water system.
Refer to the
Thermal Expansion section under Troubleshooting
Guide or contact local plumbing authority or local Sears Service
Center on how to control this situation.
NOTE: To protect against untimely corrosion of
hot
and cold
water
fittings,
it
is
strongly
recommended
that
di-electric
unions or couplings be installed on this water heater when
connected to copper pipe.
* •
CAUTION
Property Damage Hazard
• Avoid water heater damage.
• Install thermal expansion tank if necessary.
• Do not apply heat to cold water inlet.
• Contact qualified installer or Sears Service Center.
Figure 15 shows the typical attachment of the water piping to
the water heater. The water heater Is equipped with 3/4” NPT
water connections.
NOTE:
If using copper tubing, solder tubing to an adapter
before
attaching
the
adapter
to
the
cold
water
inlet
connection. Do not solder the cold water supply line directly
to the cold water inlet, it will harm the dip tube and damage
the tank.
• Look at the top cover of the water heater. The water outlet is
marked "HOT”. Put two or three turns of teflon tape around
the
threaded
end
of
the
threaded-to-sweat
coupling
and
around both ends of the 3/4” NPT threaded nipple. Using
flexible connectors, connect the hot water pipe to the hot
water outlet on the water heater.
Look at the top of the water heater. The cold water inlet Is
marked “COLD”. Put two or three turns of teflon tape around
the
threaded
end
of
the
threaded-to-sweat
coupling
and
around both ends of the 3/4” NPT threaded nipple. Using
flexible connectors, connect the cold water pipe to the cold
water inlet of the water heater.
NOTE:
This
water
heater
is
super
insulated
to
minimize
heat loss from the
tank.
Further reduction in heat loss
can
be
accomplished
by
insulating
the
hot
water
lines
from the water heater.
INSTALLATION COMPLETED USING INSTALLATION KIT
FLEXIBLE
WATER
CONNECTORS
T & P
Valve and Pipe Insulation
Remove insulation for T & P valve and pipe connections from
carton.
PIPE
INSULATION
FLUE PIPE
Fit pipe insulation over the incoming cold water line and the
hot water line. Make sure that the insulation is against the top
cover of the heater.
13