Gas piping, Wafer piping -13, Awarning – Kenmore 153.33443 User Manual
Page 16: Breathing hazard - carbon monoxide gas, Fire and explosion hazard
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
DRAFT HOOD
VENT TO OUTDOORS
OR CHIMNEY
FIGURE
17.
The vent pipe from the water heater must be no less than the
diameter of the draft hood outlet on the water heater and must
slope upward at least 1/4 inch per iinearfoot (21 mm per meter).
See Figure 18.
TO
CHIMNEY
Ali vent gases must be completely vented to the outdoors of the
structure (dwelling). Install only the draft hood provided with the
new water heater and no other draft hood,
Vent pipes must be secured at each joint with sheet metal screws.
There must be a minimum of 6 inches (153 mm) clearance
between single wall vent pipe and any combustible material.
Fill and seal any clearance between single wall vent pipe and
combustible
material
with
mortar
mix,
cement,
or
other
noncombustible substance. For other than single wall, follow
vent pipe manufacturer’s clearance specifications. To insure a
tight fit of the vent pipe in a brick chimney, seal around the vent
pipe with mortar mix cement.
AWARNING
Breathing Hazard - Carbon Monoxide Gas
Flue gases may escape if vent
pipe is not connected.
Do not store corrosive chemicals
in vicinity of water heater.
Chemical corrosion of flue and
vent system can cause serious
injury or death.
Contact
a qualified installer or
service agency.
Breathing carbon monoxide can cause brain damage
or death. Always read and understand instruction manual.
Be sure vent pipe is properly connected to prevent escape of
dangerous flue gases which could cause deadly asphyxiation.
Chemical vapor corrosion of the flue and vent system may occur
if air for combustion contains certain chemical vapors. Spray
can
propellants,
cleaning
solvents,
refrigerator
and
air
conditioner refrigerants, swimming pool chemicals, calcium and
sodium
chloride,
waxes,
bleach
and
process
chemicals
are
typical compounds which are potentiaiiy corrosive.
Gas Piping
V
AWARNING
Fire and Explosion Hazard
• Do not use water heater with
any gas other than the gas
shown on the rating plate,
•
Excessive
pressure
to
gas
control valve can cause serious
injury or death.
•
Turn
off
gas
lines
during
installation.
•
Contact qualified installer or
service agency.
Failure to have required clearances between vent piping and
combustible material will result in a fire hazard.
Make sure the gas supplied is the same type listed on the model
rating
plate.
The
inlet
gas
pressure
must
not
exceed
14 inch water column (3.5kPa) for natural and propane gas (L.P.)
gas. The minimum inlet gas pressure listed on the rating plate
is for the purpose of input adjustment. If the gas control valve is
subjected to pressures exceeding 1/2 pound per square inch
(3.5kPa), the damage to the gas control valve could result in a
fire or explosion from leaking gas.
If the main gas line shutoff serving all gas appliances is used,
also turn “OFF" the gas at each appliance. Leave all gas
appliances
shut
"OFF”
until
the
water
heater
installation
is
complete.
A gas line of sufficient size must be run to the water heater.
Consult the current edition of National Fuel Gas Code ANSI
Z223.1/NFPA 54 and your gas supplier concerning pipe size.
There must be:
•
A readily accessible manual shut off valve in the gas supply
line serving the water heater, and
•
A drip leg (sediment trap) ahead of the gas control valve to
help prevent dirt and foreign materials from entering the gas
control valve.
•
A flexible gas connector or a ground joint union between the
shut off valve and control valve to permit servicing of the unit.
Be sure to check all the gas piping for leaks before lighting the
water heater. Use a soapy water solution, not a match or open
flame. Rinse off soapy solution and wipe dry.
The minimum inlet gas pressure shown on the rating plate is
that which will permit firing at the rated input.
16