Local Access —

BACview

6

Handheld: The BACview

6

is a keypad/display

interface used to connect to the RTU Open to access the

control information, read sensor values, and test the RTU,

see Fig. 70. This is an accessory interface that does not

come with the RTU Open controller and can only be used

at the unit. Connect the BACview

6

to the RTU Open J12

local access port. There are 2 password protected levels in

the display (User and Admin). The user password is

defaulted to 0000 but can be changed. The Admin

password is 1111 and cannot be changed. There is a 10

minute auto logout if a screen is idle. See Form

48--50HCTQ--01T, Appendix A for navigation and screen

content.

Virtual BACview:

Virtual BACview is a freeware computer

program that functions as the BACview

6

Handheld. The

USB Link interface (USB--L) is required to connect a

computer to the RTU Open board. The link cable connects

a USB port to the J12 local access port. This program

functions and operates identical to the handheld.

RTU Open Troubleshooting —
Communication LEDs:
The LEDs indicate if the

controller is speaking to the devices on the network. The

LEDs should reflect communication traffic based on the

baud rate set. The higher the baud rate the more solid the

LEDs will appear. See Table 10.

Cable

Access Port

J12

P1

P1

P5

P5

RTU Open

BACview

6

Local Access Cable

Protocol Selector

C10812

Fig. 70 -- BACview

6

Handheld Connections