Step 11 — Install External Condensate Trap and

Line

The unit has one

3

/

4

-in. condensate drain connection on

the end of the condensate pan (see Fig. 21). See Figs. 1, 2

and 3, item “E”, in the view labeled “BACK

(HORIZONTAL DISCHARGE)” for the location of the

condensate drain connection.

CONDENSATE
DRAIN
CONNECTION

C10729

Fig. 21 -- Condensate Drain Pan Connection

The piping for the condensate drain and external trap can

be completed after the unit is in place. Hand tighten

fittings to the drain pan fitting. Provide adequate support

for the drain line. Failure to do so can result in damage to

the drain pan. See Fig. 22.

NOTE: Trap should be deep enough to offset maximum unit static

difference. A 4” (102) trap is recommended

.

MINIMUM PITCH

1” (25mm) PER

10’ (3m) OF LINE

BASE RAIL

OPEN

VENT

TO ROOF

DRAIN

DRAIN PLUG

ROOF

CURB

SEE NOTE

2˝ (51) MIN

C08022

Fig. 22 -- Condensate Drain Piping Details

All units must have an external trap for condensate

drainage. Install a trap at least 4-in. (102 mm) deep and
protect against freeze-up. If drain line is installed

downstream from the external trap, pitch the line away

from the unit at 1-in. per 10 ft (25 mm in 3 m) of run. Do

not use a pipe size smaller than the unit connection
(

3

/

4

-in.).

Step 12 — Make Electrical Connections

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal

injury or death.
Do not use gas piping as an electrical ground. Unit

cabinet must have an uninterrupted, unbroken electrical

ground to minimize the possibility of personal injury if

an electrical fault should occur. This ground may consist

of electrical wire connected to unit ground lug in control

compartment, or conduit approved for electrical ground

when installed in accordance with NEC (National

Electrical Code); ANSI/NFPA 70, latest edition (in

Canada, Canadian Electrical Code CSA [Canadian

Standards Association] C22.1), and local electrical

codes.

!

WARNING

NOTE: Field--supplied wiring shall conform with the
limitations of minimum 63_F (33_C) rise.
Field Power Supply —

If equipped with optional Powered Convenience Outlet:

The power source leads to the convenience outlet’s

transformer primary are not factory connected. Installer

must connect these leads according to required operation

of the convenience outlet. If an always--energized

convenience outlet operation is desired, connect the

source leads to the line side of the unit--mounted

disconnect. (Check with local codes to ensure this method

is acceptable in your area.) On a unit without a

unit--mounted disconnect, connect the source leads to the

line side with unit field power leads. See Fig. 23.

LOAD

SIDE

SEE

DETAIL

A

DETAIL

A

LINE

SIDE

BLK

YEL

BLU

CONTROL BOX

L3

L2

L1

C11181

Fig. 23 -- Location of TB1

Field power wires are connected to the unit at line--side

pressure lugs on the terminal block (see wiring diagram

label for control box component arrangement) or at

factory--installed option non--fused disconnect switch. Use

copper conductors only.
NOTE: Make field power connections directly to line
connection pressure lugs only.