Table 9 – RTU Open Controller Inputs and Outputs

POINT NAME

BACnet OBJECT

NAME

TYPE OF I/O

CONNECTION PIN

NUMBER(S)

DEDICATED INPUTS

Space Temp / Zone Temp

zone_temp

AI (10K Thermistor)

J20---1, 2

Supply Air Temperature

sa_temp

AI (10K Thermistor)

J2---1, 2

Outdoor Air Temperature

oa_temp

AI (10K Thermistor)

J2---3, 4

Space Temperature Offset Pot

stpt_adj_offset

AI (100K Potentiometer)

J20---3

Safety Chain Feedback

safety_status

DI (24 VAC)

J1---9

Compressor Safety Status

comp_status

DI (24 VAC)

J1---2

Fire Shutdown Status

firedown_status

DI (24 VAC)

J1---10

Enthalpy Status

enthalpy_status

DI (24 VAC)

J2---6

Humidistat Input Status

humstat_status

DI (24 VAC)

J5---7

CONFIGURABLE INPUTS

Indoor Air CO2

iaq

AI (4---20 ma)

J4---2 or J4---5

Outdoor Air CO2

oaq

AI (4---20 ma)

Space Relative Humidity

space_rh

AI (4---20 ma)

Supply Fan Status*

sfan_status

DI (24 VAC)

J5---1 or J5---3 or

J5 5 or J5---7

Filter Status*

filter_status

DI (24 VAC)

Door Contact Input*

door_contact_status

DI (24 VAC)

Occupancy Contact*

occ_contact_status

DI (24 VAC)

OUTPUTS

Economizer Output

econ_output

AO (4---20ma)

J2---5

Supply Fan Relay State

sfan

DO Relay (24VAC , 1A)

J1---4

Compressor 1 Relay State

comp_1

DO Relay (24VAC , 1A)

J1---8

Compressor 2 Relay State

comp_2

DO Relay (24VAC , 1A)

J1---7

Heat Stage 1 Relay State

heat_1

DO Relay (24VAC , 1A)

J1---6

Heat Stage 2 Relay State

heat_2

DO Relay (24VAC , 1A)

J1---5

Power Exhaust Relay State

pexh

DO Relay (24VAC , 1A)

J11---3

Dehumidification Relay State

dehum

DO Relay (24VAC, 1A)

J11---7, 8

LEGEND
AI

--- Analog Input

AO --- Analog Output
DI

--- Discrete Input

DO --- Discrete Output
* These inputs (if installed) take the place of the default input on the specific channel according to schematic.

Parallel pins J5---1 = J2---6, J5---3 = J1---10, J5---5 = J1---2 are used for field---installation.

The RTU Open controller requires the use of a Carrier

space sensor. A standard thermostat cannot be used with

the RTU Open system.

Supply Air Temperature (SAT) Sensor —

On FIOP--equipped 48HC unit, the unit is supplied with a

supply--air temperature (SAT) sensor (33ZCSENSAT). This

sensor is a tubular probe type, approx 6--inches (12.7 mm) in

length. It is a nominal 10--k ohm thermistor.

The SAT is factory--wired. The SAT probe is wire--tied to the

supply--air opening (on the horizontal opening end) in its

shipping position. Remove the sensor for installation.

Re--position the sensor in the flange of the supply--air

opening or in the supply air duct (as required by local

codes). Drill or punch a

1

/

2

--in. hole in the flange or duct.

Use two field--supplied, self--drilling screws to secure the

sensor probe in a horizontal orientation. See Fig. 40.

Outdoor Air Temperature (OAT) Sensor —

The OAT is factory--mounted in the EconoMi$er2 (FIOP or

accessory). It is a nominal 10k ohm thermistor attached to

an eyelet mounting ring.

EconoMi$er2 —

The RTU Open control is used with EconoMi$er2 (option

or accessory) for outdoor air management. The damper

position is controlled directly by the RTU Open control;

EconoMi$er2 has no internal logic device.

Outdoor air management functions can be enhanced with

field--installation of these accessory control devices:

Enthalpy control (outdoor air or differential sensors)
Space CO

2

sensor

Outdoor air CO

2

sensor

Field Connections

Field connections for accessory sensors and input devices

are made the RTU Open, at plugs J1, J2, J4, J5, J11 and

J20. All field control wiring that connects to the RTU

Open must be routed through the raceway built into the

corner post as shown in Fig. 31. The raceway provides the

UL required clearance between high-- and low--voltage

wiring. Pass the control wires through the hole provided in

the corner post, then feed the wires thorough the raceway

48H