isolated 24 vac power source to the sensor and to connect

the sensor to the control board terminals.

To connect the sensor to the control, identify the positive

(4 to 20 mA) and ground (SIG COM) terminals on the

sensor. See Fig. 46. Connect the 4--20 mA terminal to

RTU Open terminal J4--2 and connect the SIG COM

terminal to RTU Open terminal J4--3. See Fig. 63.

4-20mA

SIG COM

J4-2

J4-3

IAQ Sensor

24 VAC

C10738

Fig. 63 -- RTU Open / Indoor CO

2

Sensor

(33ZCSENCO2) Connections

Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus

weatherproof enclosure) —

The outdoor air CO

2

sensor is designed to monitor carbon

dioxide (CO

2

) levels in the outside ventilation air and

interface with the ventilation damper in an HVAC system.

The OAQ sensor is packaged with an outdoor cover. See

Fig. 48. The outdoor air CO

2

sensor must be located in the

economizer outside air hood.

Wiring the Outdoor Air CO

2

Sensor: A dedicated

power supply is required for this sensor. A two--wire cable

is required to wire the dedicated power supply for the

sensor. The two wires should be connected to the power

supply and terminals 1 and 2.

To connect the sensor to the control, identify the positive

(4 to 20 mA) and ground (SIG COM) terminals on the

OAQ sensor. See Fig. 46. Connect the 4 to 20 mA

terminal to RTU Open terminal J4--5. Connect the SIG

COM terminal to RTU Open terminal J4--6. See Fig. 64.

4-20mA

SIG COM

J4-5

J4-6

OAQ Sensor/RH Sensor

24 VAC

C10739

Fig. 64 -- RTU Open / Outdoor CO

2

Sensor

(33ZCSENCO2) Connections

Space Relative Humidity Sensor or Humidistat —
Humidi--MiZer

R

Control Wiring: In units equipped

with the Humidi--MiZer option there are two pink (PNK)

wires loose in the control box used to control the

dehumidification function of the unit. These pink wires

are meant to be tied to a space humidistat or thermidistat

on an electromechanical unit. On RTU Open equipped

units these pink wires must be connected to J11--7 & 8 to

allow the Open board to operate the dehumidification

function for the unit. Disconnect the J11 Phoenix style

connector from the board and use the plug screws to

secure the pink wires in pins 7 and 8, reconnect the plug

to the board at J11.
Relative Humidity Sensors (Space or Duct Mounted):

The accessory space humidity sensor (33ZCSENSRH-01)

or duct humidity sensor (33ZCSENDRH-01) is used to

measure the relative humidity of air within the space or

return air duct. The RH reading is used to control the

Humidi--MiZer option of the rooftop unit. For wiring

distances up to 500 ft (152 m), use a 3--conductor, 18 or

20 AWG shielded cable. The shield must be removed

from the sensor end of the cable and grounded at the unit

end. The current loop power for sensor is provided by the

RTU Open controller as 24vdc. Refer to the instructions

supplied with the RH sensor for the electrical

requirements and terminal locations. RTU Open

configurations must be changed after adding an RH

sensor. See Fig. 65 and 66 for typical RH sensor wiring.

S

J4--1 or J4--4 = 24vdc loop power

S

J4--2 or J4--5 = 4--20mA signal input

NOTE: The factory default for dehumidification control

is normally open humidistat.

SW2

1

2

3

4

5

6

ON

Io

Vin

Gnd

Vo

MOUNTING
HOLES

WIRING
OPENING

Vin - J4-1 or J4-4 24Vdc
Io - J4-2 or J4-5 -20mA output

C11087

Fig. 65 -- Space Relative Humidity Sensor Typical Wiring