Positioning on Curb —

Position unit on roof curb so that the following clearances

are maintained:

1

/

4

in. (6 mm) clearance between the roof

curb and the base rail inside the right and left,

1

/

2

in.

(12 mm) clearance between the roof curb and the base rail

inside the front and back. This will result in the distance

between the roof curb and the base rail inside on the

condenser end of the unit being approximately equal to

Details A and B in Figs. 6, 7 and 8.

Do not attempt to slide unit on curb after unit is set. Doing

so will result in damage to the roof curb seal.

Although unit is weatherproof, guard against water from

higher level runoff and overhangs.

Flue vent discharge must have a minimum horizontal
clearance of 48 in. (1220 mm) from electric and gas meters,

gas regulators, and gas relief equipment. Minimum distance

between unit and other electrically live parts is 48 inches

(1220 mm).

Flue gas can deteriorate building materials. Orient unit such

that flue gas will not affect building materials. Locate

mechanical draft system flue assembly at least 48 in. (1220

mm) from an adjacent building or combustible material.

After unit is in position, remove rigging skids and

shipping materials.

Step 7 — Horizontal Duct Connection

Refer to Figs. 1, 2 and 3 for locations and sizes of the

horizontal duct connections. Note that there are two different

return air duct connection locations – one for unit without an

economizer (on back side of unit) and a different one for

unit equipped with an economizer (on left end, under the

economizer hood). The supply air duct connection is on the

back side.

See Fig. 11 for top view depicting typical

horizontal duct arrangements.

Return Air Duct

with Economizer

Return Air Duct

without

Economizer

Horizontal
Supply Air

C10626

Supply

Return without

Economizer

Return with

Economizer

Location

Back

Back

Left end

Height --- In. (mm)

15

7

/

8

(402)

49

3

/

8

(1253)

18

3

/

8

(467)

Width --- in. (mm)

29

3

/

4

(756)

23

3

/

8

(593)

61

5

/

8

(1564)

Fig. 11 -- Horizontal Duct Opening Dimensions

Field--supplied

(3

/

4

--inch) flanges should be attached to

horizontal duct openings (see Fig. 11) and all ductwork

should be secured to the flanges. Insulate and weatherproof

all external ductwork, joints, and roof or building openings

with counter flashing and mastic in accordance with

applicable codes.

Step 8 — Install Outside Air Hood — Factory

Option

The outside air hood for factory--option economizer and

two--position damper is shipped in knock--down form and

requires field assembly. The panel for the hood top is

shipped on the end of the unit (see Fig. 12). The

remaining parts for the hood assembly (including side

panels, filters and tracks) are shipped in a carton that is

secured to the rear of the blower assembly. Access the

carton location through rear panel (see Fig. 13).

Hood Top

Shipping

Position

C09134

Fig. 12 -- Hood Top – Shipping Position

To remove the hood parts package:

1. Remove the back blower access panel.
2. Locate and cut the strap, being careful to not damage

any wiring.

3. Carefully lift the hood package carton through the

back blower access opening.

See Fig. 14 for identification of the various parts of the

hood assembly.

Hood

Package

C09133

Fig. 13 -- Hood Package – Shipping Location

48H