Aerco, Appendix f, Legend – AERCO KC1000 Water Heater July 2011 User Manual

Page 105: Sd -a -709

background image

APPENDIX F

F-5

CONNECT

5/

8''

I.D

. HOSE TO CONDENSATE DRAIN

SHELL DRAIN VALVE

RELIEF VALVE

SD

-A

-709

WITH STRATIFIED PEAK STORAGE TANK

KC

1000 1

MIL

. BTU LOW NOx

6)

LOCATE WATER INLET AND OUTLET FITTINGS

(i.

e.

UNIONS

, ELBOWS

, ETC

.)

A MINIMUM OF

6''

FROM WATER HEATER FITTINGS TO

3)

ALL

(*)

ITEMS ARE INCLUDED SEPARATELY IN SHIPMENT

.

TO A CONVENIENT FLOOR DRAIN

.

RELIEF VALVE SHOULD BE PIPED VERTICALLY TO A HEIGHT

18

'' ABOVE FLOOR

.

2)

SHELL DRAIN VALVE AND CONDENSATE HOSE SHOULD BE ARRANGED TO PERMIT THE FLUIDS TO DRAIN FREELY

, BY GRAVITY

,

NOTES

:

DRAIN VALVE

UNION

CHECK VALVE

STOP VALVE

5)

HOSE CONNECTION AT HEATER OUTLET IS FOR INITIAL HEATER CALIBRATION DURING START

-UP

.

(NOTE

6)

6''

4)

THIS IS A TYPICAL INSTALLATION DRAWING

.

LOCAL CODES AND AUTHORITIES SHOULD BE CONSULTED

.

1)

FOR ACTUAL SIZES AND LOCATIONS OF PIPING AND OTHER CONNECTIONS TO THE HEATER

, SEE DIMENSIONAL DRAWING

.

REMOTE ALARM CONNECTION

7.

7"

W

.C

. (

PROPANE GAS

) AT MAXIMUM BTU

/H INPUT

GAS IN

- SEE GF

-1030

FOR GAS PIPING INSTALLATION

MAINTAIN A REGULATED

8.

8"

W

.C

. PRESSURE

(NATURAL GAS

)/

1-

1/

4''

MANUAL SHUTOFF

*

DIRT TRAP

2'

JK

113006

NTS

A

D

LEGEND

TO DRAIN

T

T

SIZE INLET FOR

(NOTE

6)

6''

AT REQUIRED TEMP

. RISE

SET AT FLOW

THROTTLING VALVE

T

6''

(NOTE

6)

CONNECTION

HOSE

3:

1

PREFERRED

DIA

. RATIO

: 2

:1

MIN

.,

TANK HEIGHT TO

HOT WATER OUT

CAPACITY OF HEATER

DIA

. =

2/

3

TANK DIA

.

INLET BAFFLE

FLOW

2

FT

/SEC

PUMP

(SEE NOTE

7)

EXPANSION TANK

7)

PUMP SHOULD BE CAPABLE OF HEATER

'S RATED FLOW AT DESIGN TEMPERATURE RISE

.

FOR TWO TEMPERATURE ZONE INSTL

.

RELIEF VALVE

THERMOMETER

T

COLD WATER SUPPLY

120

°F HOT

WATER OUT

140

°F

120

°F RECIRC

TEMPERING VALVE

*

*

140

°F RECIRC

BALANCING VALVE

APPD

.

CHKD

.

DWN

.BY

SIZE

SCALE

DATE

REV

.

NORTHVALE

, NJ

07647

INTERNATIONAL

, INC

.

AERCO

8)

MOUNT TEMPERATURE SWITCH

1/

3

UP FROM THE BOTTOM OF THE TANK

, SWITCH WILL TURN PUMP ON AND OFF

.

SWITCH (NOTE

8)

TEMPERATURE

VACUUM BREAKER

BACKFLOW PREVENTER

(NOTE

12

)

BREAKER

VACUUM

(NOTE

10

)

12

) WHEN REQUIRED BY LOCAL CODES

, A VACUUM BREAKER MUST BE INSTALLED WITH THE STORAGE TANK

.

10

) IF PERMITTED BY LOCAL CODES

, A CHECK VALVE MAY BE USED IN PLACE OF A BACKFLOW PREVENTER

.

11

) CONSULT LOCAL CODES FOR PROPER TYPE OF CONNECTIONS TO STORAGE TANK

.

GAS FIRED WATER HEATER

MANDATORY GAS PRESSURE REGULATOR

(SUPPLIED BY OTHERS

)

(FOR DUAL

-FUEL INSTALLATION

, SEE NOTE

9)

(FOR DUAL

-FUEL INSTALLATION

, SEE NOTE

9)

DUAL GAS PIPING SYSTEM TO PREVENT DIRECT FLOW OF FUEL FROM ONE SYSTEM OF GAS PIPING

-

INSTALL APPROPRIATE REGULATOR FOR CURRENT FUEL IN USE

.

-

INSTALLER MUST CHECK WITH LOCAL CODES REGARDING ACCEPTABLE METHOD OF DESIGNING

INTO ANOTHER

(FOR EXAMPLE

, FROM NATURAL GAS TO PROPANE

, AND VICE VERSA

).

9)

FOR DUAL

-FUEL INSTALLATION

:

PREVENT INTERFERENCE WITH REMOVAL OF HEATER PANELS

.

WHEN A FLEX CONNECTOR IS FACTORY SUPPLIED

BY AERCO

, IT MUST BE INSTALLED AT THE HOT WATER OUTLET CONNECTION OF THE WATER HEATER

.

ALL PIPING

&

ELECTRIC CONNECTIONS

(SERVICE SWITCHES

, CONDUIT BOXES

) SHOULD BE

6"

AWAY FROM SIDE PANELS

.

LOCATE GAS PRESSURE REGULATOR A MINIMUM OF

2'

FROM HEATER

.