Clearing hardware error (hw.er) display – AERCO Modbus Communications Manual for ECS User Manual
Page 12

AC-106 INSTRUCTIONS - ECS COMMUNICATIONS
8
E r r 4
Error 4: Keyboard failure. Stuck
button or button was pressed
during power-up
Switch power off and then on, without
touching any of the controller buttons
E r r 5
Error 5: Faulty internal
communication
Check printed circuit board
interconnections. If the fault cannot be
cleared, return the controller for repair.
E r r 6
Digital filter chip faulty or loose
board inside controller
Return Controller for repair
E r r 7
PV ID failure
Return Controller for repair
E r r 8
Module 1 ID failure
Faulty or loose module, or isolation
problem
E r r 9
Module 2 ID failure
Faulty or loose module, or isolation
problem
Module 3 ID failure
Faulty or loose module, or isolation
problem
E r r A
DC output failure
Return Controller for repair
d C F
9. CLEARING HARDWARE ERROR (HW.ER) DISPLAY
To clear a Hardware Error and reset the Temperature Controller, proceed as follows:
1. Simultaneously press the Page (
) and Scroll (
) buttons on the Temperature Controller.
2. Using
the
Up
(▲) arrow button, change the password to “8”.
3. Simultaneously press the Page (
) and Scroll (
) buttons again and observe the
Temperature Controller display. The top line will display “8” and the bottom line will display “NO”.
4. Press
the
Up
(▲) arrow button to toggle the display from “NO” to “YES”.
5. Simultaneously press the Page (
) and Scroll (
) buttons to “Reset” the Temperature
Controller and clear the Hardware Error.