Clearing hardware error (hw.er) display – AERCO Modbus Communications Manual for ECS User Manual

Page 12

background image

AC-106 INSTRUCTIONS - ECS COMMUNICATIONS

8

E r r 4

Error 4: Keyboard failure. Stuck
button or button was pressed
during power-up

Switch power off and then on, without
touching any of the controller buttons

E r r 5

Error 5: Faulty internal
communication

Check printed circuit board
interconnections. If the fault cannot be
cleared, return the controller for repair.

E r r 6

Digital filter chip faulty or loose
board inside controller

Return Controller for repair

E r r 7

PV ID failure

Return Controller for repair

E r r 8

Module 1 ID failure

Faulty or loose module, or isolation
problem

E r r 9

Module 2 ID failure

Faulty or loose module, or isolation
problem

Module 3 ID failure

Faulty or loose module, or isolation
problem

E r r A

DC output failure

Return Controller for repair

d C F

9. CLEARING HARDWARE ERROR (HW.ER) DISPLAY

To clear a Hardware Error and reset the Temperature Controller, proceed as follows:

1. Simultaneously press the Page (

) and Scroll (

) buttons on the Temperature Controller.

2. Using

the

Up

(▲) arrow button, change the password to “8”.

3. Simultaneously press the Page (

) and Scroll (

) buttons again and observe the

Temperature Controller display. The top line will display “8” and the bottom line will display “NO”.

4. Press

the

Up

(▲) arrow button to toggle the display from “NO” to “YES”.

5. Simultaneously press the Page (

) and Scroll (

) buttons to “Reset” the Temperature

Controller and clear the Hardware Error.