Every 6 Months Maintenance

WARNING!

T

O

AVOID

WATER

DAMAGE

OR

SCALDING

FROM

VALVE

OPERATION

,

A

DISCHARGE

LINE

MUST

BE

CONNECTED

TO

THE

RELIEF

VALVE

OUTLET

AND

DIRECTED

TO

A

SAFE

PLACE

OF

DISPOSAL

. T

HIS

DISCHARGE

LINE

MUST

BE

INSTALLED

BY

A

QUALIFIED

SERVICE

TECHNI

-

CIAN

OR

HEATING

/

PLUMBING

INSTALLER

IN

ACCORDANCE

WITH

THE

E

STEEM

INSTALLA

-

TION

MANUAL

. T

HE

DISCHARGE

LINE

MUST

BE

TERMINATED

SO

AS

TO

ELIMINATE

POSSIBIL

-

ITY

OF

SEVERE

BURNS

OR

PROPERTY

DAM

-

AGE

SHOULD

THE

VALVE

DISCHARGE

.

• Read the temperature display and pres-

sure gauge to ensure the system is
pressurized. Lift the relief valve top lever
slightly, allowing water to relieve through
the valve and discharge piping.

• If water flows freely, release the lever

and allow the valve to seat. Watch the
end of the relief valve discharge pipe
to ensure that the valve does not weep
after the line has had time to drain. If
the valve weeps, lift the lever again to
attempt to clean the valve seat. If the
valve does not properly seat and contin-
ues to weep afterwards, contact a quali-
fied service technician to inspect the
valve and system.

• If the water does not flow from the valve

when you lift the lever completely, the
valve or discharge line may be blocked.
Immediately shut the unit down per the
instructions below. Call a qualified ser-
vice technician to inspect the valve and
system.

GF-125U