beautypg.com

Warning, 7every 6 months maintenance, Every 6 months maintenance – AERCO Esteem Users Guide User Manual

Page 10: Gf-125u

background image

7

Every 6 Months Maintenance

• Ensure the condensate drain line is

not blocked by pouring water through
the plug port on the condensate drain
assembly. The water should flow out of
the end of the drain line. If water does
not appear at the end of the drain line,
contact a qualified service technician to
inspect and clean the condensate line.

• To fill the condensate drain assembly,

if necessary, remove the plug from the
condensate assembly. Slowly pour
water into the trap assembly until water
appears at the end of the drain line.
Stop filling and replace plug.

Check Automatic Air Vents (If Used)

1. Remove the cap “A” from any automatic

air vent in the system and check opera-
tion by depressing valve “B” slightly
with the tip of a screwdriver.
See Figure 2.

2. If the air vent valve appears to be work-

ing freely and not leaking, replace cap
“A”, screwing it on fully.

3. Loosen cap “A” one full turn to allow

vent to operate properly.

4. Have the air vent replaced by a quali-

fied service technician if it does not
operate correctly.

Every 6 Months Maintenance

Check Water and Gas Piping

• Remove the boiler front jacket panel

and perform a gas leak inspection per
steps 1 through 6 of the Operating
Instructions on page 7. If gas odor
or leak is detected, immediately shut
down the unit following procedures on
page 7. Call a qualified service techni-
cian.

• Visually inspect for leaks around the

internal boiler water connections and
around the heat exchanger. Visually
inspect the external system piping, cir-
culators, and system components and
fittings. Immediately call a qualified ser-
vice technician to repair any leaks.

WARNING!

H

AVE

LEAKS

FIXED

AT

ONCE

BY

A

QUALIFIED

SERVICE

TECHNICIAN

. F

AILURE

TO

COMPLY

COULD

RESULT

IN

SEVERE

PERSONAL

INJURY

,

DEATH

OR

SUBSTANTIAL

PROPERTY

DAMAGE

.

Operate Pressure Relief Valve

• Before proceeding, verify that the relief

valve outlet has been piped to a safe
place of discharge, avoiding any possi-
bility of scalding from hot water.

A

B

Figure 2: Automatic Air Vent

GF-125U