Control panel operating procedures – AERCO BMK 3.0 LN Dual Fuel Jan 2011 User Manual
Page 30
CONTROL PANEL OPERATING PROCEDURES
3.7 TUNING MENU
The Tuning Menu items in Table 3-5 are Factory
set for each individual unit. Do not change
these menu entries unless specifically requested
to do so by Factory-Trained personnel.
3.8 COMBUSTION CAL MENU
The Combustion Cal (Calibration) Menu items in
Table 3-6 are used to vary the speed of the
unit’s blower motor based on air temperature
and air density at prescribed firing rates. This is
accomplished by providing a DC drive voltage to
the motor which adjusts the rotational speed of
the blower to maximize combustion efficiency
and ensure the unit conforms to the Nitrogen
Oxide (NOx) and Carbon Monoxide (CO)
emissions specified in Chapter 4. The firing
rates (%) and default drive voltages are listed in
Table 3-6.
Table 3-5. Tuning Menu
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
Prop Band
1°F
120°F
70°F
Integral Gain
0.00
2.00
1.00
Derivative Time
0.0 min
2.00 min
0.00 min
Reset Defaults?
Yes, No, Are You Sure?
No
Table 3-6. Combustion Cal Menu
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
CAL Voltage 16%
.25
8.20
1.80v
CAL Voltage 30%
.25
8.20
3.20v
CAL Voltage 45%
.25
8.20
3.70v
CAL Voltage 60%
.25
8.20
3.80
CAL Voltage 80%
.25
8.20
4.60
CAL Voltage 100%
.25
8.20
6.00
SET Valve Position
0%
100%
0%
Blower Output
Monitor Blower Output Voltage
.00
3.9 START SEQUENCE
When the Control Box ON/OFF switch is set to
the ON position, it checks all pre-purge safety
switches to ensure they are closed. These
switches include:
• Safety Shut-Off Valve Proof of Closure
(POC) switch
• Low Water Level switch
• High
Water
Temperature
switch
• High Gas Pressure switch
• Low Gas Pressure switch
• Blower Proof switch
If all of the above switches are closed, the
READY
light above the ON/OFF switch will light
and the unit will be in the Standby mode.
When there is a demand for heat, the following
events will occur:
NOTE
If any of the Pre-Purge safety device
switches are open, the appropriate fault
message will be displayed. Also, the
appropriate fault messages will be displayed
throughout the start sequence, if the
required conditions are not observed.
3-8