beautypg.com

Control panel operating procedures – AERCO BMK 1.5 LN May 2009 User Manual

Page 28

background image

CONTROL PANEL OPERATING PROCEDURES

Figure 3-3.

SSOV Locations

3. With all required safety device switches

closed, a purge cycle will be initiated and the
following events will occur:

(a) The Blower relay energizes and turns

on blower.

(b) The Air/Fuel Valve rotates to the full-

open purge position and closes purge
position switch. The dial on the Air/Fuel
Valve (Figure 3-4) will read 100 to
indicate that it is full-open (100%).

(c) The FIRE RATE bargraph will show

100%.

4. Next, the blower proof switch on the Air/Fuel

Valve (Figure 3-5) closes. The display will
show Purging and indicate the elapsed time
of the purge cycle in seconds. The normal
(default) time for the purge cycle is 7
seconds.

5. Upon completion of the purge cycle, the

Control Box initiates an ignition cycle and
the following events occur:

(a) The Air/Fuel Valve rotates to the low-

fire ignition position and closes the
ignition switch. The dial on the Air/Fuel
Valve (Figure 3-6) will read between 25
and 35 to indicate that the valve is in
the low-fire position.

(b) The igniter relay is activated and

provides ignition spark.

(c) The gas Safety Shut-Off Valve (SSOV)

is energized (opened) allowing gas to
flow into the Air/Fuel Valve.

100

DETAIL “A”

DIAL

(DETAIL “A”)

STEPPER

MOTOR

Figure 3-4.

Air/Fuel Valve In Purge Position

Figure 3-5.

Blower Proof Switch

6. Up to 7 seconds will be allowed for ignition

to be detected. The igniter relay will be
turned off one second after flame is
detected.

7. After 2 seconds of continuous flame, Flame

Proven

will be displayed and the flame

strength will be indicated. After 5 seconds,
the current date and time will be displayed in
place of the flame strength.

3-8