Installing Belimo Motorized Valves on AERCO Benchmark Boilers

Technical instruction Document

TID-0028_0C














Figure 2: Multiple Boiler Piping Schematic Showing Motorized Valve Locations for

AERCO KC1000 Boilers

3. Valve Orientation

The valve can be oriented in any position as long as the actuator does not go below the horizontal plane.

See orientation guide from Belimo that is attached to the valve.

4. Valve Wiring

See

Table 1 on the next page to determine which of the included diagrams to use.

IMPORTANT NOTE!

The valves are supplied with 3 feet of power cable (exception:

Valve PN 92084-7 is supplied with Screw Terminal for electrical

connection) and 3 feet of auxiliary switch cable. If the cables are

not long enough, we recommend that a distribution box be

connected. The power and auxiliary cables are permanently

connected to the valve and cannot be removed.