Hardy Advantage Weigh Modules LPB User Manual
Page 29

OPERATION AND INSTALLATION MANUAL
Page 23
Step 1.
Use a millivolt meter or Integrated Techni-
cian feature (See Physical Checks, Step 6)
and measure the LPS output under “no
load” conditions. The reading should be
less than 1% of the full scale output.
NOTE:
Sensors can shift up to about 10% of their full scale
and still function correctly.
Step 2.
If the output has shifted more than 1%,
replace the sensor.
Assumption: A 5VDC excitation on a sensor with a
3mV/V output sensitivity, a 1% shift in zero balance
will yield a 0.1 mV/V change from the specification.
Bridge
Resistance Test
Problem: Changes in Bridge Resistance
Cause: Failure of a compensating element, or by a
broken or burned bridge wire. Often cause by an elec-
trical transient such as lightning.
Remedy:
Step 1.
Use an Ohmmeter and measure the resis-
tance between the EXC + and EXC- leads.
The value for the EXC leads should be
1106 ohms + - 5 ohms.
Step 2.
Use an Ohmmeter and measure the resis-
tance between the SIG + and SIG - leads.
The value for the SIG leads should be
1,000 ohms + - 1 ohm.
Step 3.
Readings that exceed the ranges indicated
suggest damage and the load cell should
be thoroughly inspected or replaced.
Resistance to
Ground Test
Problem:Electrical leakage is creating an
unstable output from the instru-
ment.
Cause: Water contamination in the load
sensors or cables.