Deg f) – Carrier AQUAZONE 50PEC09-18 User Manual
Page 60

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500052-01
Printed in U.S.A.
Form 50PEC-2SI
CL-2
7-09
Replaces: 50PEC-1SI
Copyright 2009 Carrier Corporation
-
- -
- -
-
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
-
- -
- -
-
--
- -
-
- -
- -
-
- -
-
- -
-
- -
- - -
CUT
AL
ONG DO
TT
E
D
LINE
CU
T ALONG DO
TT
E
D
LINE
HEATING CYCLE ANALYSIS
COOLING CYCLE ANALYSIS
HEAT OF EXTRACTION (ABSORPTION) OR HEAT OF REJECTION =
FLOW RATE (gpm) x
TEMP. DIFF. (DEG. F) x
FLUID FACTOR* =
(Btu/hr)
SUPERHEAT = SUCTION TEMPERATURE – SATURATED SUCTION TEMPERATURE
=
(DEG F)
SUBCOOLING = SATURATED CONDENSING TEMPERATURE – LIQUID LINE TEMPERATURE
=
(DEG F)
*Use 500 for water, 485 for antifreeze.
SUCTION
COMPRESSOR
DISCHARGE
COAX
EXPANSION
VALVE
F
F
AIR
COIL
F
ft wg
WATER OUT
WATER IN
F
ft wg
LOOK UP PRESSURE DROP IN TABLE 12
TO DETERMINE FLOW RATE
F
LIQUID LINE
ft wg
F
SST
(SATURATED
SUCTION
TEMPERATURE)
a50-8453
SUCTION
COMPRESSOR
DISCHARGE
COAX
EXPANSION
VALVE
F
F
AIR
COIL
F
ft wg
WATER OUT
WATER IN
F
ft wg
LOOK UP PRESSURE DROP IN TABLE 12
TO DETERMINE FLOW RATE
F
LIQUID LINE
ft wg
F
SST
(SATURATED
SUCTION
TEMPERATURE)
a50-8454
97B0035N06