HEATING CYCLE ANALYSIS

COOLING CYCLE ANALYSIS

HEAT OF EXTRACTION (ABSORPTION) OR HEAT OF REJECTION =

FLOW RATE (gpm) x

TEMP. DIFF. (DEG. F) x

FLUID FACTOR* =

(Btu/hr)

SUPERHEAT = SUCTION TEMPERATURE – SATURATED SUCTION TEMPERATURE

=

(DEG F)

SUBCOOLING = SATURATED CONDENSING TEMPERATURE – LIQUID LINE TEMPERATURE

=

(DEG F)

*Use 500 for water, 485 for antifreeze.

SUCTION

COMPRESSOR

DISCHARGE

COAX

EXPANSION

VALVE

F

F

AIR

COIL

F

ft wg

WATER OUT

WATER IN

F

ft wg

LOOK UP PRESSURE DROP IN TABLE 12
TO DETERMINE FLOW RATE

F

LIQUID LINE

ft wg

F

SST
(SATURATED
SUCTION
TEMPERATURE)

a50-8453

SUCTION

COMPRESSOR

DISCHARGE

COAX

EXPANSION

VALVE

F

F

AIR

COIL

F

ft wg

WATER OUT

WATER IN

F

ft wg

LOOK UP PRESSURE DROP IN TABLE 12
TO DETERMINE FLOW RATE

F

LIQUID LINE

ft wg

F

SST
(SATURATED
SUCTION
TEMPERATURE)

a50-8454