APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)

LEGEND

SCREEN NAME

POINT NAME

PASSWORD

LEVEL

EDITABLE

RANGE

DEFAULT

NOTES

Configuration

Unit

Configuration

Fan Mode

Admin Password

level access only

X

Auto/Continuous/

Always On

Continuous

Auto= Intermittant operation during both

occupied and unoccupied periods/

Continuous = Intermittant during unoccupied

periods and continuous during occupied

periods/Always on = fan operates

continuously during both occupied and

unoccupied periods

Fan On Delay

X

0 - 30 sec

10 sec

Defines the delay time before the fan begins

to operate after heating or cooling is started

Fan Off Delay

X

0 - 180 sec

45 sec

Defines the amount of time the fan will

continue to operate after heating or

cooling is stopped

Heating Enable

X

Disable/Enable

Enable

Provides capability to manually

disable heating operation

Cooling Enable

X

Disable/Enable

Enable

Provides capability to manually

disable cooling operation

Minimum SAT in

Cooling

X

40 - 60

F

50

F

Defines the minimum acceptable operating

temperature for the Supply Air

Maximum SAT in

Heating

X

80 - 140 F

110 F

Defines the maximum acceptable operating

temperature for the Supply Air

Damper Ventilation

Position

X

0 - 100%

100%

Normally set to 100% if 2 position damper

type or set to minimum ventilation position if

damper type = DCV

DCV Maximum Vent

Position

X

0 - 100%

100%

Usually set at 100% - Used to limit maximum

damper opening in DCV mode

Filter Alarm Timer

X

0 - 9999 hrs

0 hrs

Disables Filter Alarm if set to 0

Pushbutton Override

X

Disable/Enable

Enable

Enables Override Feature on Rnet sensor

SPT Sensor Set Point

Adjustment

X

Disable/Enable

Enable

Enables Set Point adjustment capability

on Rnet Sensor

Lockout Cooling if

OAT <

X

-65 - 80 F

-65 F

Cooling is locked out when OAT is less than

configured value and OAT is actively being

broadcast

Lockout Heating if

OAT >

X

35 - 150 F

150 F

Heating is locked out when OAT is greater

than configured value and OAT is actively

being broadcast

Power Fail Restart

Delay

X

0 - 600 sec

60 sec

Delay before equipment starts

Occupancy Schedules

X

Disable/Enable

Enable

Enables unit occupied

Set Point Separation

X

2 - 9 F

4 F

Used to enforce minimum

set point separation

Configuration

Service

Test

Test Mode

Admin Password

level access only

X

Disable/Enable

Disable

Used to enable test mode. Will automatically

reset to disable after 1 hour

Fan Test

X

Disable/Enable

Disable

Used to test all fan speeds. Sequences fan

from low to high and operates each speed for

1 minute. Resets to disable on completion

Fan Speed

Off/Low Speed/Medium

Speed/High Speed/On

Displays current fan operation

Compressor Test

X

Disable/Enable

Disable

Used to test compressor cooling and heating

operation. Sequences cooling stage 1, then

stage 2, then heating stage 2 and reduces

capacity to stage 1. Operates for 1 minute per

step. Resets to disable on completion.

Dehumidification Test

X

Disable/Enable

Disable

Used to test dehumification mode -

Operates for 2 minutes. Resets to

disable on completion.

Testing Compressor

Inactive/Heating/Cooling/

Dehumidify/TimeGard

Wait

Displays compressor test mode

Aux Heating Test

X

Disable/Enable

Disable

Used to test auxiliary heat.

Sequences fan on and enables

heating coil for 1 minute. Resets to

disable on completion

H

2

O Economizer Test

X

Disable/Enable

Disable

Used to test entering/return air water loop

economizer coil operation. Sequences fan on

and opens economizer coil water valve for 1

minute. Resets to disable on completion

Preposition OA

Damper

X

Disable/Enable

Disable

Used to preposition OA damper

actuator to set proper preload

Open Vent

Damper 100%

X

Disable/Enable

Disable

Used to test OA damper operation

SAT

F

Displays SAT

LCWT

F

Displays Leaving Condenser

Water Temperature

°

°

°

°

°

°

°

°

°

°

°
°

BAS — Building Automation System
DCV — Demand Controlled Ventilation
IAQ

Indoor Air Quality

OAT

Outdoor Air Temperature

RH

Relative Humidity

SAT

Supply Air Temperature

SPT

Space Temperature

TPI

Third Party Integration