beautypg.com

Step 5 — wire low voltage connections – Carrier AQUAZONE 50PEC09-18 User Manual

Page 30

background image

30

Table 2 — Electrical Data — 50PEC Units

LEGEND

Step 5 — Wire Low Voltage Connections

WATER FREEZE PROTECTION — The Aquazone™ con-

trol allows the field selection of source fluid freeze protection

points through jumpers. The factory setting of jumper JW3

(FP1) is set for water at 30 F. In earth loop applications, jumper

JW3 should be clipped to change the setting to 10 F when

using antifreeze in colder earth loop applications. See Fig. 30.

ACCESSORY CONNECTIONS — Terminal labeled A on

the control is provided to control accessory devices such as

water valves, electronic air cleaners, humidifiers, etc. This

signal operates with the compressor terminal. See Fig. 31.

Refer to the specific unit wiring schematic for details.
NOTE: The A terminal should only be used with 24-v signals

— not line voltage signals.

WATER SOLENOID VALVES — An external solenoid

valve(s) should be used on ground water installations to shut

off flow to the unit when the compressor is not operating. A

slow closing valve may be required to help reduce water

hammer. Figure 31 shows typical wiring for a 24-vac external

solenoid valve. Figures 32 and 33 illustrate typical slow closing

water control valve wiring for Taco 500 Series and Taco ESP

Series valves. Slow closing valves take approximately 60 sec.

to open (very little water will flow before 45 sec.). Once fully

open, an end switch allows the compressor to be energized

(only on valves with end switches). Only relay or triac based

electronic thermostats should be used with slow closing valves.

When wired as shown, the slow closing valve will operate

properly with the following notations:

1. The valve will remain open during a unit lockout.
2. The valve will draw approximately 25 to 35 VA through

the “Y” signal of the thermostat.

50PEC

UNIT SIZE

VOLTAGE

CODE

V-PH-Hz

MIN/MAX

VOLTAGE

COMPRESSOR

FAN MOTOR

FLA

TOTAL UNIT

FLA

MIN CIRCUIT

AMPS

MAX

FUSE/HACR

QTY

RLA

LRA

09

1

115-1-60

104/126

1

8.1

46.5

0.6

8.6

10.7

15

3

208/230-1-60

197/254

1

4.5

23.0

0.4

4.9

6.0

15

4

265-1-60

239/292

1

3.1

24.0

0.4

3.5

4.3

15

12

1

115-1-60

104/126

1

10.6

55.8

1.0

11.6

14.3

25

3

208/230-1-60

197/254

1

5.2

24.0

0.6

5.8

7.1

15

4

265-1-60

239/292

1

4.2

25.0

0.4

4.6

5.7

15

15

3

208/230-1-60

197/254

1

6.1

30.0

0.8

6.9

8.4

15

4

265-1-60

239/292

1

4.7

28.5

0.6

5.3

6.5

15

18

3

208/230-1-60

197/254

1

6.8

38.0

0.7

7.5

9.2

15

4

265-1-60

239/292

1

6.2

29.0

0.6

6.8

8.4

15

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
LRA

Locked Rotor Amps

RLA

Rated Load Amps

IMPORTANT: Connecting a water solenoid valve can

overheat the anticipators of electromechanical thermo-

stats. Only use relay based electronic thermostats.

AQUAZONE CONTROL (Complete C Control Shown)

Fig. 30 — Typical Aquazone Control Board

Jumper Locations

a50-7467tf

Typical

Water

Valve

C

A

24 VAC

Terminal Strip

Fig. 31 — Typical Aquazone Accessory Wiring

Fig. 32 — AMV Valve Wiring

C

C

THERMOSTAT

1

Y

1

2

3

1

Y

AMV

TACO VALVE

HEATER SWITCH

a50-8441

Fig. 33 — Taco SBV Valve Wiring

a50-8442