C006 Output Control Configuration - Configures the output controls of the Comfort Plus Commercial
system. To determine the value, check the options desired from the list below. Then, add the numbers
from the Value column and enter the sum into this location.
Value
Option Selected
3
All 6100 Series Systems.
8
Enables compressor control if there is a "COOL" call during a peak (control) time.
32
If it is a peak (control) period and the Comfort Plus Commercial receives a cooling call,
the compressor will turn off and on in 20 minute intervals (off 20 minutes, on 20 minutes,
off 20 minutes, etc.).
128
Interfaces Comfort Plus Commercial with a heat pump that has a reversing valve which
is energized for heating.
C007
Charge Factor - This configuration should be set to a value of 30.
C008 through C010 configurations are only applicable if the Comfort Plus Commercial system is
being used in conjunction with a heat pump.
C008
Heat Pump Compressor Outdoor Lock-Out Temperature for Off-Peak or Anticipated Peak
Modes - Indicates the outdoor temperature at which the heat pumps compressor is locked out and not
allowed to operate during an off-peak or anticipated peak period.
C009
Heat Pump Compressor Outdoor Lock-Out Temperature for On-Peak Mode - Indicates the
outdoor temperature at which the heat pumps compressor is locked out and not allowed to operate
during an on-peak period.
C010
Minimum Discharge Air Temperature - Sets the minimum discharge air temperature the system
targets during a Stage 1 heat call.
C011
Currently not utilized in the 6100 Comfort Plus Commercial systems.
C012
Currently not utilized in the 6100 Comfort Plus Commercial systems.
C013-C021 Time Clock Module Configuration - These configuration settings are used to configure the peak
control times when utilizing the optional Steffes Time Clock Module. Refer to the installation and
configuration instructions included with the time clock module for more information.