beautypg.com

Carrier 58TMA User Manual

Page 5

background image

g. Flame-sensing electrode.

h. Wiring connectors leading to control.

6. Remove 8 screws that secure flue collector box to center

panel. Be careful not to damage sealant.

7. Remove complete inducer assembly from furnace, exposing

flue openings.

8. Using field-provided small wire brush, steel spring cable,

reversible electric drill, and vacuum cleaner, clean cells as
follows:

a. Assemble wire brush and steel spring cable.

(1.) Use 48 in. of 1/4-in. diameter high-grade steel spring

cable (commonly known as drain clean-out or Roto-
Rooter cable).

(2.) Use 1/4-in. diameter wire brush (commonly known as

25-caliber rifle cleaning brush).

NOTE:

The materials needed in items (1.) and (2.) can usually be

purchased at local hardware stores.

(3.) Insert twisted wire end of brush into end of spring

cable, and crimp tight with crimping tool or strike with
ball-peen hammer. TIGHTNESS IS VERY IMPOR-
TANT.

(4.) Remove metal screw fitting from wire brush to allow

insertion into cable.

b. Clean each heat exchanger cell.

(1.) Attach variable-speed, reversible drill to end of spring

cable (end opposite brush).

(2.) Remove cell outlet plates. IMPORTANT: Replace

screws in center panel before cleaning.

(3.) Insert brush end of cable into upper opening of cell

and slowly rotate with drill. DO NOT force cable.
Gradually insert at least 36 in. of cable into 2 upper
passes of cell. (See Fig. 8.)

(4.) Work cable in and out of cell 3 or 4 times to obtain

sufficient cleaning. DO NOT pull cable with great
force. Reverse drill and gradually work cable out.

(5.) Remove burner assembly and cell inlet plates.

NOTE:

Be very careful when removing the burner assembly to

avoid breaking the ignitor. See Fig. 9 for the correct ignitor
location.

(6.) IMPORTANT: Replace screws in center panel and

cells before cleaning.

(7.) Insert brush end of cable in lower opening of cell, and

proceed to clean 2 lower passes of cell in same manner
as 2 upper passes.

(8.) Repeat foregoing procedures until each cell in furnace

has been cleaned.

(9.) Using vacuum cleaner, remove residue from each cell.

(10.) Using vacuum cleaner with soft brush attachment,

clean burner assembly.

(11.) Reinstall cell outlet plates and screws FIRST; then,

reinstall cell inlet plates and burner assembly. Care
must be exercised to center the burners in the cell
openings.

9. After cleaning flue openings, check sealant on flue collector to

ensure that it has not been damaged. If new sealant is needed,
contact your dealer or distributor.

10. Clean and replace flue collector assembly, making sure all 8

screws are secure.

11. Reinstall relief box.

12. Reconnect wires to the following components:

a. Draft safeguard switch.

b. Inducer motor.

c. Pressure switches.

d. Limit overtemperature switch(es).

e. Gas valve.

f. Hot surface ignitor.

g. Flame-sensing electrode.

h. Wiring connectors leading to control.

13. Reconnect vent pipe to relief box. When applicable replace

vent pipe enclosure.

14. Replace blower door only.

15. Turn power and gas to ON.

16. Set thermostat and check furnace for proper operation.

17. Verify blower airflow and speed changes between heating and

cooling.

Fig. 8—Cleaning Heat Exchanger Cell

A91252

Fig. 9—Position of Ignitor to Burner

A93347

BURNER

IGNITOR

11 32

"

7 8

"

C

L

C

L

IGNITOR
ASSEMBLY

CELL
PANEL

BURNER

13 32

"

HOT
SURFACE
IGNITOR
ASSEMBLY

5