beautypg.com

Help key, Header setting, Sensor diagnostic – Eclipse Combustion EGA4 User Manual

Page 41: 3 help key, 1 header setting, 2 sensor diagnostic

background image



Instruction Manual MM850481 ed.01

When you select the Alarms option, the following page will be displayed:

ALARMS

Alarm 1: O2

Enabled

: Yes

Thresh.

: 5.00

Type

: Min

ESCAPE

NEXT

Use the [S] and [T] keys to move the cursor symbol to the desired option.

Press the [ENTER] key to change the value.

Press [ESCAPE] (F1) to return to the previous menu.

Press [NEXT] (F1) to display the next alarm page. Up to 4 alarms can be set for different gas type and levels.


N

OTE

:

THE REFERENCE GAS FOR ALARMS ARE PROGRAMMED IN FACTORY

. T

HE GAS TYPE CAN BE CHANGED ONLY USING THE

OPTIONAL

PC

CONFIGURATION SOFTWARE

.


When the measured value became in alarm band, a continuous sound (beep) inform you the condition. Simultaneously,
the parameter will be displayed in the measuring page in reverse mode. You can acknowledge the alarms pressing the
[ENTER] key. In this case the beep will stop but the reverse mode remain.

9.3 HELP

key

Help menu inform of the instrument status (electrochemical cells status and battery level), Service information and allows
you to change the header printer text.
When you select this option, the following page will be displayed:

HELP

HEADER PRINTER

SENSOR DIAGNOSTIC

Batt. 100%

ESCAPE

SERVICE


Press [ESCAPE] (F2) to return to the previous page.

9.3.1 Header

setting

The “HEADER PRINTER” option, allows you to set 4 rows of 16 characters for report header printing.
Press the [ENTER] key when the cursor symbol is positioned near the menu option. The following page will be displayed:

HEADER PRINTER

R1

R2
R3

R4

ESCAPE


Select the R1, R2, R3, and R4 rows and press [ENTER] to insert or change the text.
Press [ESCAPE] (F2) to return to the previous page.

9.3.2 Sensor

Diagnostic

The “SENSOR DIAGNOSTIC” option, allows you to read the actual status for the inserted cells.
Press the [ENTER] key when the cursor symbol is positioned near the menu option. The following page will be displayed:

41