beautypg.com

Viewing and entering setpoints (cutoffs) – Dillon FI-90 User Manual

Page 15

background image

15

A setpoint cutoff is a force-load value at which an internal electrical connec-

tion is broken, causing an external relay to de-energize. Additional relay

configurations can turn on or shut off another electrical device.
You may configure the FI-90 to accept either one of two types of cutoff: (1) a

gross-based setpoint or (2) an increment-based setpoint. A gross-based

setpoint is called, simply, a setpoint. With this type of setpoint, activation of

a cutoff is signaled by a specified gross applied force. You specify, through

the front-panel keypad, the gross force-load setpoint that will activate each

cutoff. For example, suppose your first cutoff requires 100 pounds of force,

and your second cutoff requires 200 pounds of force; you would set the first

setpoint at 100 pounds of force and the second setpoint at 300 pounds of

force, because those values will represent gross force load when the cutoffs

activate.
With the increment-based setpoint, activation of a cutoff is signaled by a

specified amount of net force. You tell the indicator the net amount of force

required to activate each of the cutoffs. Suppose your first cutoff requires 100

pounds of force, and your second cutoff requires 100 pounds of force; you

would enter 100 for setpoint #0 and 100 for setpoint #1.
You can view the type of setpoint that has been configured in your indicator

by looking at the cutoff display in the operations menu. A decimal point

following the word cutoff indicates configuration of gross-based setpoints. If

no decimal point appears after cutoff, the FI-90 is configured for increment-

based setpoints.

1. Starting from either gross mode or

peak-view mode, press MENU

twice to access. . .

CutOFF.0 The decimal after CutOFF

says this is a gross-based setpoint.

Then press PRINT / SELECT. . .

nn.n is displayed. The n 's represent

the current value in register 0 .

Viewing and Entering Setpoints (Cutoffs)

The two setpoint registers are

numbered #0 and #1.