Input Firing Range

:

High Fire (Max.)
High Fire (Min.)
Low Fire (Max.)
Low Fire (Min.)

USA

Canada

USA

Canada

USA

Canada

1,500 MBH

800 MBH
560 MBH
350 MBH

1,370 MBH

800 MBH
560 MBH
350 MBH

2,700 MBH
1,300 MBH

990 MBH
550 MBH

2,300 MBH
1,300 MBH

990 MBH
550 MBH

5,000 MBH
2,000 MBH
1,400 MBH

730 MBH

4,000 MBH
2,000 MBH
1,400 MBH

730 MBH

Fuel:
Natural Gas
Propane (LP)

0.6 Specifi c Gravity Typical
1.53 Specifi c Gravity Typical

0.6 Specifi c Gravity Typ.
1.53 Specifi c Gravity Typ.

0.6 Specifi c Gravity Typ.
1.53 Specifi c Gravity Typ.

Gas Train:
Standard
Options

UL Listed / CSD-1 confi guration
IRI, FM

UL Listed / CSD-1 confi guration
IRI, FM

UL Listed / CSD-1 confi guration
IRI, FM

Gas Train Inlet Pressure:
Minimum
Maximum

3.7” WC*
10 PSI

3.5” WC*
10 PSI

3.5” WC*
10 PSI

Manifold to Furnace
Pressure Drop:
**
Highest High Fire
Lowest High Fire

3.7” WC
2.7” WC

3.5” WC
2.5” WC

3.5” WC
2.5” WC

Firing Modes Available:

Low Fire Start
High/Low
Modulation

-
High/Low
Modulation

-
High/Low
Modulation

Standard Flame
Safeguard:
Low Fire Start
High / Low
Modulation

RM7897A
RM7897C
RM7897C

-
RM7897C
RM7840L

-
RM7897C
RM7840L

Flame Detector:
Standard

UV

UV

UV

Airfl ow Proving Switch:

Standard

Standard

Standard

Gas Pressure Switches:

Standard High and Low

Standard High and Low

Standard High and Low

Ignition:

Direct Ignition of Main Flame

Direct Ignition of Main Flame

Direct Ignition of Main Flame

Motor:
HP
RPM
Standard Voltage
Motor FLA
Optional Voltages

1/2HP
3450 RPM
120 volt, 1 ph, 60 Hz
6.4 Amps @120 volt AC
208/230v, 1 ph, 60 Hz
208/230v, 3 ph, 60 Hz
460v, 3 ph, 60 Hz
575v, 3 ph, 60 Hz

3/4 HP
3450 RPM
120 volt, 1 ph, 60 Hz
10.4 Amps @120 volt AC
208/230v, 1 ph, 60 Hz
208/230v, 3 ph, 60 Hz
460v, 3 ph, 60 Hz
575v, 3 ph, 60 Hz

2 HP
3450 RPM
208/230v, 1 ph, 60 Hz
13.4 Amps @230 volt AC
208/230v, 3 ph, 60 Hz
460v, 3 ph, 60 Hz
575v, 3 ph, 60 Hz

Weight:

125 lbs.

145 lbs.

165 lbs.

Dimensions:

Refer to Figures 4 & 5.

*See manufacturer’s nameplate settings for specifi c minimum gas pressure requirements.
** See Figures 14A, 14B, & 14C.
† Canada High Fire rate is reduced to accomodate 25% reserve air.

Table 1 – Burner Specifi cations

Figure 1 - Burner Label Location

Section: Pre-installation Checklist

General Model Information

Serial Number,

Including Date Code

Rating Information

Approval Agency Symbols

Fuel

R.W. Beckett Construction
& Setting Data

R.W. Beckett Specifi cation
Number and Revision

Boiler Manufacturer and
Model, When Applicable