beautypg.com

Beckett CG50 User Manual

Page 21

background image

21

CG15, CG25, CG50 Burner Manual

Table 3 - Initial Burner Settings for Both Propane & Natural Gas

Furnace Pressure at High Fire

0” W.C.

0.25” W.C.

0.50” W.C.

1.00” W.C.

High Fire Rate MBH

Low Fire Rate MBH

Burner Model

Low Fire Gas Pressure, inch WC

Low Fire Damper Setting

High Fire Gas Pressure, inch WC

High Fire Damper Setting

Low Fire Gas Pressure, inch WC

Low Fire Damper Setting

High Fire Gas Pressure, inch WC

High Fire Damper Setting

Low Fire Gas Pressure, inch WC

Low Fire Damper Setting

High Fire Gas Pressure, inch WC

High Fire Damper Setting

Low Fire Gas Pressure, inch WC

Low Fire Damper Setting

High Fire Gas Pressure, inch WC

High Fire Damper Setting

CG15

800

468

CG15.1S

0.9

9

2.7

25

1.0

9

2.9

26

1.1

9

3.2

27

1.3

10

3.7

31

900

468

CG15.1S

0.9

9

3.4

32

1.0

9

3.7

34

1.1

9

3.9

37

1.2

10

4.4

43

950

548

CG15.2S

0.9

12

2.6

30

0.9

13

2.9

33

1.0

13

3.1

36

1.2

14

3.6

42

1050

548

CG15.2S

0.9

12

3.2

38

0.9

13

3.4

48

1.0

13

3.7

58

1.1

14

4.2

84

1150

641

CG15.3S

0.9

16

2.8

42

0.9

17

3.1

49

1.0

17

3.3

56

1.2

19

3.8

74

1250

641

CG15.3S

0.9

16

3.3

52

0.9

17

3.6

68

1.0

17

3.8

85

-

-

-

-

1300

750

CG15.4S

0.9

20

2.7

51

1.0

21

2.9

66

1.0

22

3.2

80

-

-

-

-

1400

750

CG15.4S

0.9

20

3.1

66

1.0

21

3.3

100

-

-

-

-

-

-

-

-

CG25

1350

669

CG25.1S

0.7

17

2.7

38

0.7

17

3.0

38

0.8

17

3.2

39

0.9

18

3.7

41

1450

669

CG25.1S

0.7

17

3.1

41

0.7

17

3.4

41

0.8

17

3.6

42

0.9

18

4.1

41

1550

774

CG25.2S

0.7

20

2.7

41

0.7

20

2.9

42

0.8

21

3.2

43

0.9

23

3.7

46

1700

774

CG25.2S

0.7

20

3.2

48

0.7

20

3.4

49

0.8

21

3.7

51

0.9

23

4.2

56

1800

896

CG25.3S

0.7

23

2.7

54

0.7

23

2.9

55

0.8

24

3.2

56

0.9

26

3.7

60

2000

896

CG25.3S

0.7

23

3.3

66

0.7

23

3.6

68

0.8

24

3.8

70

0.9

26

4.3

78

2100

1037

CG25.4S

0.7

27

2.8

66

0.7

27

3.1

71

0.8

28

3.3

76

0.9

30

3.8

90

2300

1037

CG25.4S

0.7

27

3.4

84

0.7

27

3.6

93

0.8

28

3.9

102

-

-

-

-

2400

1200

CG25.5S

0.6

30

2.5

85

0.7

30

2.8

100

0.8

31

3.0

115

-

-

-

-

2500

1200

CG25.5S

0.6

30

3.0

100

0.7

30

3.2

115

-

-

-

-

-

-

-

-

CG50

2000

888

CG50.1S

0.5

7

2.4

20

0.5

7

2.6

20

0.6

7

2.9

21

0.7

8

3.4

23

2200

888

CG50.1S

0.5

7

3.1

22

0.5

7

3.3

23

0.6

7

3.6

24

0.7

8

4.1

26

2400

1044

CG50.2S

0.5

8

2.5

23

0.5

8

2.8

24

0.6

9

3.0

25

0.7

10

3.5

28

2700

1044

CG50.2S

0.5

8

3.2

28

0.5

8

3.5

29

0.6

9

3.7

30

0.6

10

4.2

34

2900

1228

CG50.3S

0.5

9

2.6

27

0.5

9

2.9

28

0.6

10

3.1

29

0.6

11

3.6

33

3200

1228

CG50.3S

0.5

9

3.2

31

0.5

9

3.5

33

0.6

10

3.7

35

0.6

11

4.2

41

3400

1443

CG50.4S

0.5

11

2.7

33

0.5

11

2.9

35

0.6

12

3.2

37

0.7

13

3.7

42

3800

1443

CG50.4S

0.5

11

3.3

44

0.5

11

3.6

46

0.6

12

3.8

48

0.6

13

4.3

54

4000

1700

CG50.5S

0.5

13

2.7

50

0.5

13

3.0

52

0.6

14

3.2

54

0.7

17

3.7

60

4500

1700

CG50.5S

0.5

13

3.5

70

0.5

13

3.7

76

0.6

14

4.0

82

0.6

17

4.5

96

4800

1700

CG50.5S

0.5

13

4.0

98

0.5

13

4.2

115

-

-

-

-

-

-

-

-

Gas pressures are as measured at the manifold test connection.

Notice: The settings in this chart are for reference only. The actual conditions at the installation may require further
adjustment by the fully qualifi ed and experienced start-up technician.
Notice: The light-off rate must not be set below the low fi re recommendation. Lower rates will lengthen the time it takes
for gas to get to the burner head and may cause ignition failures.

Section: Start the Burner

This manual is related to the following products: