Troubleshooting

LCD Display Messages

If the APS scanner detects a problem or fault during use, it is shown on the LCD display.

Fault

Check

Comments

The pedestal is no longer
maintaining consistent and
accurate absolute positioning.

Check the laser scanner window for dust
contamination and clean as necessary.

See Laser Scanner Window on page 16.

Check the laser scanner window for possible
damage (scratches, cracks or fracture).

If the window is damaged it may need to be replaced.
Contact Vinten Radamec customer support.

The APS scanner is not updating
or displaying pedestal positional
information.

Check that the APS scanner is set to navigation
mode.

On the scanner mode page, click on the Navigation
Mode
button to return the APS system to normal
operation.

Check that the APS scanner is set to the correct
layer number for the current studio location.

See Managing Layers on page 13.

Display

Fault/Check

Comments

Communication or power problem with the APS scanner.
Check all interconnections and that the pedestal is
powered up.

See Electrical Connections on page 7.

Communication has not been established between the

APS scanner and the pedestal. Check that the pedestal is

powered up and working with the control system.