Up and Down Buttons

To view the “High Temp” recorded by the
cooling unit, press the “Up” button once.

To view the “Low Temp” recorded by the
cooling unit, press the “Down” button
once.


To reset the “High Temp” or “Low Temp”,
press the “Set” button for three seconds
while “Hi” or “Lo” is displayed. “RST” will
blink three times to indicate confirmation.

Set Button

The cooling unit is factory preset with a
Minimum Set Point of 14.4°C and a
Temperature Differential of 2.2°C. This
means that the cooling unit will turn on
when the display rises above 16.6°C
(14.4°C + 2.2°C), and turn off when the
display falls below 14.4°C. In this example,
the average temperature inside the cellar
will be 15.6°C.

To view the Minimum Set Point, press the
“Set” button for one second.

To change the Minimum Set Point,

 Press the “Set” button for three

seconds until °C” blinks

 Press “Up” or “Down” button
 Press “Set” button to confirm


The “Set” temperature will blink three
times to indicate confirmation

The recommended Minimum Set Point
range is 11.7 – 15.6°C. To change the
Temperature Differential, see “Advanced
Operation” later in this chapter.