Step 1.

Verify that 115V is present between "L1" and "L2"
on terminal strip, (See Diagram M).

Check circuit breaker or fuse

and electrical connections.

SideShot and appliance are not interlocked correctly
or malfunction of appliance controls. Refer to
electrical diagrams in this manual and appliance
manufacturer's troubleshooting guide.

Replace Timer/Relay,
Part #950-1067.

No

No

No

Yes

Yes

Yes

SYMPTOM 3: SIDESHOT MOTOR WILL NOT OPERATE

Replace Motor, Part #950-0625.

Step 2.

With thermostat calling for heat, check for voltage
between "O" and "R" of terminal strip.

Step 3.

Verify that 115V is present between "M" and "L2"
on timer/Relay.