ProgressiveRC 6S PowerLog User Manual
Page 18

-18-
Multifunctional Monitor & Logger PowerLog 6S
4. Alarm Settings: Select【Alarm setting】, press <
> and the screen shows:
<▲> or <▼> to select items, press <
> button to confirm, press < >
for more than 3 seconds to return.
See details below.
<▲> or <▼> to select items, press <
> button to confirm and the
item will be with
⊙
, press <
> for more than 3 seconds to confirm the
amendment and return.
When the measured value exceeds the set alarm limit value, the
alarm triggers, sends out signal. When the measured value goes back
to the normal status, if set ‖Toggle‖, the alarm output recovers to
normal; if set ‖Hold‖, the alarm output remains.
【
Toggle NO.】 Toggle mode, normal open
【
Toggle NC.】Toggle mode, normal close
【
Hold NO.】Hold mode, normal open
【
Hold NC.】Hold mode, normal close
<▲> or <▼> to select the items, and press <
> to shift select /,
press <
> for 3 seconds to confirm the amendment and return.
【
Delay Time】Delay a period of time after powering on and then
begins to monitor alarm cases.
【
Logging】After entering ‖Start logging…‖ status, it begins to monitor
alarm cases.
【
Pass Through】 The measured value is between the normal value
range, and then it begins to monitor alarm cases.
For example, the normal working current of one machine is 25A, set
current alarm MIN. = 20A MAX. = 30A. If powering on PowerLog first
and then the machine, since C=0 during this period, it will trigger MIN
alarm. If set【Pass Through】, it will avoid this undesirable alarm.
ALARM SETTING
Signal Outpu
Activation
ALARM ACTIVATION
Delay Time
Logging
Pass Through
ALARM OUTPUT
⊙Toggle NO.
○Toggle NC.
○Hold NO.
○Hold NC.