beautypg.com

Kontron CP3-CMM1 User Manual

Page 8

background image

Operating Instructions

Chassis Monitoring Module (CP3-CMM1)

31.01.2003

8

Finally recalculate the binary figure to a decimal
figure. For example, binary 11111111 is decimal
255. Enter the calculated decimal figure. Press
to save the configuration.

Preset of digital outputs to “active high” or

“active low”

X = 0: output transistor is high-impedance in the
alarm-mode and low impedance in Non-alarm-
mode (idle-mode)
X = 1: output transistor is low-impedance in the
alarm-mode and high impedance in Non-alarm-
mode (idle mode)

Address 7

Bit

7

Bit

6

Bit

5

Bit

4

Bit

3

Bit

2

Bit

1

Bit

0

fix

1

1

1

1

OUT0

x

OUT1

x

OUT2

x

OUT3

x

Sum:

1

x

x

x

x

1

1

1

Default
(Decimal 255):

1

1

1

1

1

1

1

1

Address 8

Bit

7

Bit

6

Bit

5

Bit

4

Bit

3

Bit

2

Bit

1

Bit

0

fix

1

1

OUT4

x

OUT5

x

OUT6

x

OUT7

x

OUT8

x

OUT9

x

Sum:

1

1

x

x

x

x

x

x

Default:
(Decimal 255)

1

1

1

1

1

1

1

1

Preset of digital inputs to “active high” or

“active low”

X = 0: digital input is GND in Alarm state and open
or +5V in non-alarm state (idle state)
X = 1: digital input is open or +5V in Alarm state
and GND in non-alarm state (idle state)

Address 9

Bit

7

Bit

6

Bit

5

Bit

4

Bit

3

Bit

2

Bit

1

Bit

0

fix
DIN1

x

DIN2

x

DIN3

x

DIN4

x

DIN5

x

DIN6

x

DIN7

x

DIN8

x

Sum:

x

x

x

x

x

x

x

x

Default:
(Decimal 255)

1

1

1

1

1

1

1

1

Adresse 10

Bit

7

Bit

6

Bit

5

Bit

4

Bit

3

Bit

2

Bit

1

Bit

0

fix

1

0

0

0

0

0

DIN9
DIN10
DIN11
DIN12
DIN13
DIN14

x

DIN15

x

Sum:

1

x

x

0

0

0

0

0

Default:
(decimal 224)

1

1

1

0

0

0

0

0

Remark: The digital input DIN0 (Sysfail is X by

default and cannot be modified)

Setting of temperature alarm thresholds

The temperature thresholds are entered directly in
degree centigrade. The minimum temperature that
can be entered is 20°C and the maximum
temperature is 70°C.

Threshold A:
xx = temperature in °C

Address 16

Temperature

xx

Default:

60

Threshold B:
xx = temperature in °C

Address 15

Temperature

xx

Default:

40

Remark: There is no rule on which of the two
thresholds is the lower and which one is the higher
one. The LED “Temp Fail” output switches the LED
on when the lower threshold is exceeded.

activation/deactivation of voltage

measurement

You can selectively activate or deactivate the
voltage measurement of each voltage input. If a
voltage input is deactivated, also the respective
LED output is deactivated.

X = 0: voltage input deactivated
X = 1: voltage input activated

Address 11

Bit

7

Bit

6

Bit

5

Bit

4

Bit

3

Bit

2

Bit

1

Bit

0

fix

0

0

V1 ((+3.3V)

x

V2 (+5V)

x

V3 (+12V)

x

V4 (+24V)

x

V5 (-12V)

x

V6 (-24V)

x

Sum:

0

0

x

x

x

x

x

x

Default:
(Decimal 63)

0

0

1

1

1

1

1

1