Alarm messages:

X = 0: No output of the alarm message
X = 1: Output of the alarm message

Address 50

Bit

7

Bit

6

Bit

5

Bit

4

Bit

3

Bit

2

Bit

1

Bit

0

fix

0

0

0

0

Alarm OUT0

x

Alarm OUT1

x

Alarm OUT2

x

Alarm OUT3

x

Sum:

0

0

0

0

x

x

x

x

Default:
(Decimal 127)

0

0

0

0

1

1

1

1

Address 51

Bit

7

Bit

6

Bit

5

Bit

4

Bit

3

Bit

2

Bit

1

Bit

0

fix

0

0

Alarm OUT4

x

Alarm OUT5

x

Alarm OUT6

x

Alarm OUT7

x

Alarm OUT8

x

Alarm OUT9

x

Sum:

0

0

x

x

x

x

x

x

Default:
(Default xxx)

0

0

1

1

1

1

1

1

Conjunction of Input parameters with digital outputs

The input parameters can individually be assigned to the 10 digital outputs. If more than one input parameter is
assigned to an output, the inputs are logically OR-wired to the output.

Bit =1: Input parameter assigned to output
Bit =0: Input not assigned to output

23

22

21

20

19

18

17

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Ouput

Input pa

ramet

ers

nc

nc

V

6

(-24V

) o

ut of tol

erance

V

5

(-12V

) o

ut of tol

erance

V

4

(+

24V

) out of

tolera

nce

V

3

(+

12V

) out of

tolera

nce

V

2

(+

5V

) out of t

o

leranc

e

V

1

(+

3.3V

) out o

f toler

ance

nc

F

C

M

-A

u

x

ilia

ry

FC

M-T

emp

Fai

l

FC

M-F

anF

ai

l

DIN14 OR DIN15 / AC-

fail_1

OR AC-

fail_2

SYSR

ESET

a

k

ti

v

e

Tempe

ratu

rr T

h

res

h

o

ld

1

Tempe

ratu

re T

h

reshol

d

2

B

roken wire of

T

e

m

p

. S

e

nsor

DI

N0

/

SYSF

AI

L

_

in

DIN3 OR DIN4 / DE

G_in_3 OR DE

G_in_4

DIN1 OR DIN2 / DE

G_in_1 OR DE

G_in_2

DIN8 / FA

L_in_4

DIN7 / FA

L_in_3

DIN6 / FA

L_in_2

DIN5 / FA

L_in_1

OUT0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

1

0

0

0

0

0

0

0

Address 19

Address 18

Address 17

OUT1

0

0

0

0

0

0

0

0

0

0

0

0

0

0

1

1

0

0

0

0

0

0

0

0

Address 22

Address 21

Address 20

OUT2

0

0

0

0

0

0

0

0

0

0

1

0

0

0

0

0

0

0

0

0

0

0

0

0

Address 25

Address 24

Address 23

OUT3

0

0

0

0

0

0

0

0

0

0

0

1

0

0

0

0

0

0

0

0

0

0

0

0

Address 28

Address 27

Address 26

OUT4

0

0

0

0

0

0

0

0

0

0

0

0

1

0

0

0

0

0

0

0

0

0

0

0

Address 31

Address 30

Address 29

OUT5

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

1

0

0

0

0

0

0

Address 34

Address 33

Address 32

OUT6

0

0

0

0

1

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Address 37

Address 36

Address 35

OUT7

0

0

1

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Address 40

Address 39

Address 38

OUT8

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

1

1

0

0

0

0

Address 43

Address 42

Address 41

OUT9

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

1

1

1

1

Address 46

Address 45

Address 44

Remark: The table shows the CMM default conjunction of input parameters to digital outputs