2 set firmware parameters, Set firmware parameters, Ipmi firmware user guide cp6002 – Kontron CP6002 IPMI User Manual
Page 28
IPMI Firmware User Guide
CP6002
Page 28
ID: 1039-1613, Rev. 2.0
10.2
Set Firmware Parameters
This command permits the selection of interrupts to be used during KCS communication.
Please note that parameters which are set while the board is write protected are only valid until
the next IPMI firmware reset.
Table 6:
Set Firmware Parameters
COMMAND
LUN
NetFn
CMD
Set Firmware Parameters
03h
OEM = 3Eh
05h
REQUEST DATA
Byte
Data Field
1
Reserved
B4h
2
Reserved
90h
3
Reserved
91h
4
Reserved
8Bh
5
Cmd Flags
[6:2] Reserved
[1] 0b = get only, 1b = set parameters
[0] 0b = do not reset,
1b = reset Management Controller after setting
parameters
6
Operating Modes
[7:5] Reserved
[4] 0b = IPMB dual-ported, 1b = IPMB single-ported (default)
[3:1] Reserved
[0] 0b = BMC, 1b = SMC
7
IRQ number
FFh = do not use interrupts
0Ah = use IRQ10
0Bh = use IRQ11
Any other values = Reserved
RESPONSE DATA
Byte
Data Field
1
Completion code
2
Cmd flags
3
Operating modes
4
IRQ number