beautypg.com

Leading specifications, Setup, Hardware hookup – Crestron electronic RS-232/42 User Manual

Page 10

background image

Ethernet RS-232/422 COM Module

Crestron CEN-COM

RTS (COM A / B)

If RTS/CTS handshaking is enabled, these LEDs illuminate when the CEN-COM is
ready to receive data from a serial device attached to the respective COM ports.

CTS (COM A / B)

These LEDs illuminate when the serial device on the respective COM port is ready
to accept data from the CEN-COM. This “Clear to Send” signal is available only if
RTS/CTS handshaking is enabled; signal is controlled by external serial device. If
CTS signal is not connected (in cable), the signal is held high and the LEDs are
extinguished.

Leading Specifications

The table below provides a summary of leading specifications for the CEN-COM
module. Dimensions and weight are rounded to the nearest thousandth unit.

Leading Specifications of the CEN-COM

SPECIFICATION

DETAILS

Power Requirements

12 or 24 VDC, Load Factor of 2.5 Watts

SIMPL™ Windows®

Version 1.30.01 or later

1

with the addition of

smwlib45.exe and smwlib45.txt

CNX Upgrade File

Version 5.04.11 or later

2

Crestron Database

Version 11.7.210 or later

1

CEN-COM Upgrade File

Version 1.23 or later

1

Dimensions & Weight

Height: 1.70 in (4.32 cm)

Width: 6.94 in (17.63 cm)
Depth: 6.32 in (16.06 cm)
Weight: 1.90 lb (0.86 kg)

1

The latest software versions can be obtained from the Software Downloads page (SIMPLWIN,
CRESDB, and UPGRADES Libraries) of Crestron’s website (

www.crestron.com)

. New users are

required to register in order to obtain access to the FTP site.

2

Filenames for CNX upgrades have a .upz extension and can be obtained from the Software Downloads
page (OPSYS Library) of the Crestron website.

As of the date of manufacture, the unit has been tested and found to comply with
specifications for CE marking.

NOTE: This device complies with part 15 of the FCC rules. Operation is subject to
the following two conditions: (1) these devices may not cause harmful interference,
and (2) these devices must accept any interference received, including interference
that may cause undesired operation.

Setup

Hardware Hookup

Refer to the hookup diagram after this paragraph. Other than making the power
connection last, complete the connections in any order. The only connection not

6

Ethernet RS-232/422 COM Module: CEN-COM

Operations Guide - DOC. 5719