Chateau™ Decorative Gas Appliance

20009543

Horizontal Termination

The vent must rise vertically a minimum of 24”
(610 mm) off the top of the unit, before the first elbow.
The horizontal run may extend up to 20’ (6 m) and
include a vertical rise of up to 40’ (12 m). (Fig. 14) Hori-
zontal termination must also meet the criteria shown in
Figures 11 & 12.

Approved vent systems must terminate above and
including the heavy line in Figure 14.

Two 45° elbows may be substituted for each single
90° elbow.

With a rise between 2’ - 4’, one (1) 90° or two (2) 45°
elbows may be used.

Vertical Termination

A vertical vent system must terminate no less than 12’
(3.66 m) and no more than 40’ (12 m) above the appli-
ance flue collar. A 2’ (610 mm) vertical section must be

��
��
��
��
��
��
��
��
��
��




���
���



� �

� �� �� �� �� �� �� �� �� �� �� ��

Vertical Run (in feet)

(Measured from the appliance flue collar to the top of the vent

pi

pe.)

Horizontal Run (in feet)

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

• • • • • • • • • • • •
• • •• • • • • • •
• • ••• • • •• •••••••••••
• • • ••• • •••••••••
• •• • • • • • • •
• •• • •• • ••• ••••••••••••••

May use up to

three (3) 90°

elbows, but must

not have two (2)

consecutive 90°

elbows in horizon-

tal plane

Unacceptable vent-

ing configuration

FP1359

Fig. 14 Horizontal vent termination window.

May use

one (1)

elbow

only

Restrictor Plate Guide

Application

NG

LP

SK8DVSK or

2’ (610mm) vertical elbow,

2’ (610mm) horizontal

None

None

4’ (1.2m) vertical elbow

4¹⁄₂” flue

10’ (3m) horizontal elbow

None

restrictor

8’ (2.4m) vertical

12’ (3.7m) vertical & greater 6³⁄₄” flue

6³⁄₄” flue

restrictor restrictor

proper sealing. Be sure to always attach straps on up-
per elbow to a structural framing member.
For vertical installations, continue installing the pipe as
required until pipe is installed up through the ceiling. At
this point, you must install a firestop spacer.

installed before any offset. A maximum of 20’ (6.1 m)
horizontal and three (3) 90° elbows may be installed
with a minimum of 12’ (3.66 m) vertical section above
the flue collar of the unit. Refer to Page 13, Figure 15
for more information.
A vertically terminated vent system must also conform
to the following criteria:

No more than three (3) 90° elbows may be used.

Two (2) 45° elbows may be substituted for one (1)
90° elbow. No more than six (6) elbows may be
used.

Vent must rise a minimum of 2’ (610 mm) before
offset is used.

Termination height must conform to roof clearance
as specified in Figure 35.

• • • • • • • • • • • •
• • •• • • • • • • • • • •
•• • •• •••• •• • • • • • • • • • • • • •
• •• • • • • •

Pipe Section

Pipe

Rim

Pipe

Rim

Hem

Lance

FP1468

Fig. 13 Install pipe, listening for the snap-lock to fasten.

UP