beautypg.com

Caution – Carrier ROOMTOP 50AH024-096 User Manual

Page 7

background image

7

Table 1 — Physical Data

LEGEND

*Shipping weights include base unit plus packaging.

†If components are to be split, additional refrigerant will be needed.

NOTE: If components are to be split, the maximum length of refrigerant
tubing to be used is 50 equivalent ft, assuming components will be
installed in same horizontal plane. If components are not to be installed
in same horizontal plane, contact your Carrier representative for more
information. For additional piping information, refer to Carrier System
Design Manual, Part 3.

UNIT 50AH

024

036

048

OPERATING WEIGHT (lb)

Base Unit

903

910

952

Evaporator/Condenser Sections

399/484

401/489

417/515

SHIPPING WEIGHT (lb)*

1036

1043

1085

REFRIGERANT TYPE

R-410A

Operating Charge (lb-oz)†

4-5

4-5

8-8

COMPRESSOR — TYPE

Scroll

Quantity...Model

1...ZP20K5E

1...ZP31K5E

1...ZP38K5E

Oil (oz)

25

25

42

HPS Setting (psig)

Cutout

650 ± 7

Reset

Manual Reset

LPS Setting (psig)

Cutout

75 ± 7

Reset

100 ± 7

CONDENSATE DRAIN CONNECTION

Size (in.)...Type

7

/

8

...OD

CONDENSER COIL

Copper Tubes — Aluminum Fins

Size (L x H) (in.)

40 x 30

40 x 30

90 x 30

Number of Rows...Fins/in.

4...14

4...14

2...12

CONDENSER FAN

Centrifugal — Belt Drive

Nominal Cfm

1700

2000

2500

Blower Size (in.)

15 x15

15 x 15

15 x 15

Motor Hp (Rpm)

Standard Motor

0.33 (1725)

0.33 (1725)

0.33 (1725)

Upgrade 1 Motor

0.50 (1725)

Upgrade 2 Motor

0.75 (1725)

EVAPORATOR COIL

Copper Tubes — Aluminum Fins

Size (L x H) (in.)

32 x 16

32 x 16

32 x 26

Number of Rows...Fins/in.

3...12

3...12

3...14

EVAPORATOR AIR FAN

Centrifugal — Belt Drive

Nominal Cfm

800

1200

1600

Blower Size (in.)

12 x 9

12 x 9

12 x 9

Motor Hp (Rpm)

Standard Motor

0.25 (1725)

0.33 (1725)

0.33 (1725)

Upgrade 1 Motor

0.33 (1725)

0.50 (1725)

0.50 (1725)

Upgrade 2 Motor

0.50 (1725)

0.75 (1725)

0.75 (1725)

Upgrade 3 Motor

1.00 (1725)

1.00 (1725)

INDOOR-AIR FILTERS

Factory-Supplied Disposable Type

Number...Size (in.)

2...18 x 24 x 1

2...18 x 24 x 1

2...18 x 24 x 1

INTERCONNECTING TUBING SIZE

Suction (Qty...in.)

1...

5

/

8

1...

5

/

8

1...

7

/

8

Liquid (Qty...in.)

1...

3

/

8

1...

3

/

8

1...

3

/

8

Fig. 6 — Rigging Details

CENTER OF GRAVITY

NOTE: Fasten threaded rods through holes in end frames as shown.
Use 4 rods on each side of unit for a total of 8.

UNIT 50AH

DIMENSIONS (in.)

A

B

024

29.0

25.6

036

28.8

26.0

048

29.0

27.0

060

28.8

26.8

072

59.3

31.2

096

60.0

31.5

CAUTION

All panels must be in place when rigging.

HPS — High-Pressure Switch
LPS

Low-Pressure Switch