Carrier ROOMTOP 50AH024-096 User Manual
Page 11

11
Table 2B — Electrical Data — Upgrade 1 Evaporator Motor with Standard Condenser Motor
Table 2C — Electrical Data — Upgrade 2 Evaporator Motor with Standard Condenser Motor
LEGEND
UNIT
50AH
V-PH
(60 Hz)
VOLTAGE
RANGE
COMPRESSOR
FAN MOTORS
POWER SUPPLY
Evaporator
(Upgrade 1)
Condenser
(Standard)
Min
Max
QTY
RLA
LRA
Hp
FLA
Hp
FLA
Min Ckt
Amps
MOCP
Amps
024
208/230-1
187
254
1
13.5
58.0
1
/
3
1.7
1
/
3
1.7
20.3
35
036
208/230-1
187
254
1
16.7
79.0
1
/
2
2.5
1
/
3
1.7
25.1
40
208/230-3
187
254
10.4
73.0
1
/
2
1.8
1
/
3
1.3
16.1
25
460-3
414
508
5.8
38.0
1
/
2
0.9
1
/
3
0.7
8.8
15
048
208/230-1
187
254
1
19.9
109.0
1
/
2
2.5
1
/
3
1.7
29.1
50
208/230-3
187
254
13.6
83.1
1
/
2
1.8
1
/
3
1.3
20.1
35
460-3
414
508
6.1
41.0
1
/
2
0.9
1
/
3
0.7
9.2
15
060
208/230-1
187
254
1
26.4
134.0
1
/
2
2.5
1
/
3
1.7
37.2
65
208/230-3
187
254
16.0
110.0
1
/
2
1.8
1
/
3
1.3
23.1
40
460-3
414
508
7.8
52.0
1
/
2
0.9
1
/
3
0.7
11.3
20
072*
208/230-1
187
254
2
16.7
79.0
3
/
4
3.2
1
4.2
45.0
60
208/230-3
187
254
10.4
73.0
3
/
4
2.4
1
3.2
29.0
40
460-3
414
508
5.8
38.0
3
/
4
1.2
1
1.6
15.9
20
096*
208/230-1
187
254
2
19.9
109.0
1
4.2
1
1
/
2
6.5
55.5
75
208/230-3
187
254
13.6
83.1
1
3.2
1
1
/
2
4.8
38.6
50
460-3
414
508
6.1
41.0
1
1.6
1
1
/
2
2.4
17.7
25
UNIT
50AH
V-PH
(60 Hz)
VOLTAGE
RANGE
COMPRESSOR
FAN MOTORS
POWER SUPPLY
Evaporator
(Upgrade 2)
Condenser
(Standard)
Min
Max
QTY
RLA
LRA
Hp
FLA
Hp
FLA
Min Ckt
Amps
MOCP
Amps
024
208/230-1
187
254
1
13.5
58.0
1
/
2
2.5
1
/
3
1.7
21.1
35
036
208/230-1
187
254
1
16.7
79.0
3
/
4
3.2
1
/
3
1.7
25.8
40
208/230-3
187
254
10.4
73.0
3
/
4
2.4
1
/
3
1.3
16.7
25
460-3
414
508
5.8
38.0
3
/
4
1.2
1
/
3
0.7
9.1
15
048
208/230-1
187
254
1
19.9
109.0
3
/
4
3.2
1
/
3
1.7
29.8
50
208/230-3
187
254
13.6
83.1
3
/
4
2.4
1
/
3
1.3
20.7
35
460-3
414
508
6.1
41.0
3
/
4
1.2
1
/
3
0.7
9.5
15
060
208/230-1
187
254
1
26.4
134.0
3
/
4
3.2
1
/
3
1.7
37.9
65
208/230-3
187
254
16.0
110.0
3
/
4
2.4
1
/
3
1.3
23.7
40
460-3
414
508
7.8
52.0
3
/
4
1.2
1
/
3
0.7
11.6
20
072*
208/230-1
187
254
2
16.7
79.0
1
4.2
1
4.2
46.0
60
208/230-3
187
254
10.4
73.0
1
3.2
1
3.2
29.8
40
460-3
414
508
5.8
38.0
1
1.6
1
1.6
16.3
20
096*
208/230-1
187
254
2
19.9
109.0
1
1
/
2
6.5
1
1
/
2
6.5
57.8
80
208/230-3
187
254
13.6
83.1
1
1
/
2
4.8
1
1
/
2
4.8
40.2
55
460-3
414
508
6.1
41.0
1
1
/
2
2.4
1
1
/
2
2.4
18.5
25
HACR — Heating, Air Conditioning, and Refrigeration
Hp
— Horsepower
FLA
— Full Load Amps
LRA
— Locked Rotor Amps
MOCP — Maximum Overcurrent Protection (HACR breaker)
RLA
— Rated Load Amps
*Unit has two compressors.