beautypg.com

Servicing first and second checks, Sizes: 2 – Ames Fire & Waterworks 5000CIV Cast Iron Reduced Pressure Detector Assemblies User Manual

Page 5

background image

5

Servicing First and Second Checks

Sizes: 2

1

2

" – 10" (65-250mm)**

CAUTION

!

1. Remove the hatch cover bolts. The 5000CIV is designed so that

when the bolts are backed off

1

2

", all the spring load is re leased

from the cover and retained by the check module. Be sure to

verify this before removing all the bolts.

2. Lift the check valve module straight out taking care not to hit and

damage the seating.

3. The seat ring may be removed and replaced by:

Sizes 4" – 10" (100-250mm)** pulling out the two wire retainers.

Sizes 2

1

2

" – 3" (65-80mm)** twisting one quarter-turn removes

the seat.

The wire retainers are 10" long. One is drawn out clockwise and

the other is drawn out counterclockwise.

4. The seat ring can be lifted straight up and removed.
5. To replace the disc on sizes 2

1

2

" – 4" (65-100mm)** simply

remove the re tain ing nut or for sizes 6" – 10" (150-250mm)**

remove the allen head socket screws. Reverse this procedure to

install the new disc.

*Disc & Spring

As sem bly

seat

seat O-ring

Cover O-ring

2

1

2

" – 3" (65-80mm)**

*Disc & Spring

As sem bly

Retainer wire

seat O-ring

Cover O-ring

4" – 10" (100-250mm)**

lower stem

O-ring (6" only)

seat

disc

For further details contact your tech ni cal sales representative.

No special tools

required to service

First and second checks

are not interchangeable

First

Check

second

Check

Relief

Valve

WARNING

!

*Spring as sem bly is factory assembled. DO NOT DIS AS SEM BLE

** Metric Dimensions are nominal pipe diameter. This product is

produced with ASME/ANSI flanged end connections.