beautypg.com

Basic installation instructions, Maintenance instructions, Guidelines – Ames Fire & Waterworks C300Na Stainless Steel Double Check Detector Assemblies with Bi-Link Check Valves User Manual

Page 2: Instructions

background image

2

WARNING

!

Prior to servicing any Ames valve, it is mandatory to shut down the

water system by closing both the inlet and outlet shutoff valves.

WARNING

!

While the spring mechanism is removed for check

servicing, never pull the screwdriver out or off the support notches
on the arbors. Doing so may cause bodily injuries. Keep fingers out
of seat and clapper area.

After shutoff valves are closed, open test cock #2, #3 & #4 to relieve

pressure within the backflow assembly.(Figure C on page 6.)
1. After #3 test cock has been opened to relieve pressure, remove

#3 test cock from housing. (Figure A)

2. Insert a #3 screwdriver through the hole on the top of the cover

sleeve and using both hands rotate the cover sleeve approxi-

mately

1

/

4

-turn clockwise and

1

/

4

-turn counter-clockwise to break

the sleeve O-ring seals. Using the screwdriver, slowly slide the

cover sleeve to the downstream side of the housing. (Figure B)

3. Remove the stainless steel check retainer from the housing.

(Figure B)

4. Remove the #1 check module (Figure C) by inserting two flat

blade screwdrivers into the slots on either side of the check

module and gently pry the check module toward the open zone.

5. Remove #2 check module with the same instructions as in #4

above.

6. To clean or inspect either check module, insert a #3

screwdriver through the downstream side of the check module

as shown in Figure D & E. When the screwdriver is in place,

remove the “E”-clip (Figure F) and pin connecting the structural

members and the check clapper will open with no tension.

7. Thoroughly clean the seating area. The sealing disc may be

removed, if necessary, by removing the screws connecting the

keeper plate to the clapper. The sealing disc may be reversed

and reinstalled if the elastomer is cut or damaged.

8. Wash check module and O-ring and inspect for any damage. If

damaged, reinstall new parts.

9. After thorough cleaning, lubricate O-ring w/FDA approved lu-

bricant, replace pin and “E”-clip in structural members, remove

screw driver and reinstall check modules and assemble housing

in reverse order of these instructions.

Basic Installation Instructions

Guidelines

Most field problems occur because dirt and debris present in the system at the time of

installation becomes trapped in the check valves.

The system should be flushed before

the valve is installed. If the system is not flushed until after the valve is installed, remove

both check modules from the valve and open the inlet shutoff to allow water to flow for a

sufficient time to flush debris from the water line. If debris in the water system continues

to cause fouling, a strainer can be installed upstream of the backflow assembly.

The Series C200a and C300a may be installed in either horizontal or vertical position

as long as the backflow assembly is installed in accordance with the direction of the

flow arrow on the assembly and the local water authority approves the installation.

The assembly should be installed with adequate clearance around the valve to allow

for inspection, testing and servicing. 12” (300mm) should be the minimum clearance

between the lower portion of the assembly and the floor or grade.

NOTICE

Assembly body should not be painted.

Figure D

Figure E

Figure F

Figure A

Figure B

Figure C

Maintenance Instructions

Instructions

Horizontal Installation

Vertical

Installation

This manual is related to the following products: