Ames Fire & Waterworks 6000HMB Portable Hydrant Meter Backflow Preventers with Meter Housing User Manual

Page 7

background image

7

Problem Identification Procedures

Troubleshooting Guide

PROBLEM

CAUSE

SOLUTION

A. Assembly discharges from differential

relief valve during no flow condition.

Fouled first check
Fluctuating inlet pressure
Outlet pressure higher than inlet pressure

& leak in No. 2 check valve
Leak through diaphragm or around flange

bolt holes of relief valve
Pressure relief valve does not close

Disassemble and clean No. 1check valve
Control supply line water pressure
Disassemble, clean #2 check valve &

identify cause of back pressure.
Service relief valve (page 3)

See problem D

B. Assembly discharges from differential

relief valve during a flow condition.

No. 1 check valve wedged open
O-ring displaced from groove in 1st check
Pressure relief valve does not close

Fluctuating line pressure

Disassemble and clean No. 1 check valve
Disassemble and replace
See problem D

C. Differential pressure relief valve does

not open during test due to leaking

outlet gate valve.

Differential pressure across No. 1 check

valve stays above 2psi due to leaking

outlet gate valve
Weak or broken relief valve spring
Shut off seat tube bound in body
Plugged hydraulic hose

Repair shut-off valves

Disassemble and replace relief valve spring
Disassemble and repair
Disassemble and repair

D. Pressure relief valve does not close

Debris on sealing surface
Plugged hydraulic hose
Damaged seat or rubber shut off disc
Ruptured diaphragm
Wrinkled or improperly installed diaphragm

Remove relief valve and clean
Disassemble and clean
Remove relief valve assembly and replace
Disassemble and replace diaphragm
Disassemble and properly position

diaphragm

When using differential pressure gauge:

A. Check differential across No. 1 check valve
READING

PROBLEM

2 to 3 psid

Leak in No. 1 or No. 2 check valve

4 to 7 psid and steady

Malfunctioning pressure relief valve

2 to 7 psid

Inlet pressure fluctuation

Without using differential pressure gauge:

A. Close gate valve No. 2
RESULT

PROBLEM

If discharge stops

Leak in No. 2 check valve

If discharge does not stop Go to B
B. Open No. 4 testcock to produce a flow greater than

differential relief valve discharge

RESULT

PROBLEM

If discharge stops

Leak in No. 1 check valve

If discharge does not stop Malfunctioning pressure relief valve