Ames Fire & Waterworks ATG-1 Backflow Preventer Test Kit User Manual

Page 3

background image

3

1. When using differential pressure gauge

A. Check differential across No. 1 check valve
Reading Problem
2 to 3 PSID

Leak in No. 1 or No. 2 check valve

4 to 7 PSID and steady

Malfunctioning pressure relief valve

2 to 7 PSID fluctuating

Inlet pressure fluctuating

2. Without using differential pressure gauge.

A. Close gate valve No. 2
Result Problem
If discharge stops

Leak in No. 2 check valve

If discharge does not stop

Go to B

B. Open No. 4 test cock to product a flow greater

than differential relief valve discharge
Result Problem
If discharge stops

Leak in No. 1 check valve

If discharge does not stop

Malfunctioning pressure

relief valve

Problem Identification Procedures - For RPZ Assemblies

PROBLEM: Continuous or intermittent discharge from relief valve.