Figure 4 shows all possible switching patterns.

Messdistanz

Schaltbit/Schaltausgang

30mm

200mm

0

1

A

B

Werkskennlinie

(Kennlinie 1)

0

1

Invertierte Kennlinie

(Kennlinie 2)

A

0

1

Kennlinie Schaltfenster

(Kennlinie 3)

B

B

0

1

A

Invertierte Kennlinie Schaltfenster

(Kennlinie 4)

Figure 4: all possible switching patterns

5.2.3.1 Examples for numerical Teach-in:

1) An “ON” threshold shall be set at 130mm distance (B) -> (characteristic 1).

Setting the switching function:
Switching- / Teach function: 0

Point A absolute in tenth of mm:

65535

 FFFF hex (= Switching point A)

(Must be set to 65535 since only one switching point required)
Point B absolute in tenth of mm:

1300

 0514 hex (= Switching point B)

Parameter to be written:
Switching points work:

FFFF0514 hex

2) An “OFF” threshold shall be set at 70mm distance (A) -> (characteristic 2).

Setting the switching function:
Switching- / Teach function: 0

Point A absolute in tenth of mm:

700

 02BC hex (= Switching point A)

Point B absolute in tenth of mm:

65535

 FFFF hex (= Switching point B)

(Must be set to 65535 since only one switching point required)

Parameter to be written:
Switching points work:

02BCFFFF hex

factory characteristic
(characteristic 1)

inverted characteristic
(characteristic 2)

Switching window characteristic
(characteristic 3)

Inverted switching window
characteristic
(characteristic 4)

Measuring distance

switching bit / switching output