Baumer BA UNxK09 IO User Manual
Page 11

en_BA_UNXK 09-IO-Link.doc
11/18
Baumer Electric AG
24.04.2012/haa
Frauenfeld, Switzerland
Figure 4 shows all possible switching patterns.
Messdistanz
Schaltbit/Schaltausgang
30mm
200mm
0
1
A
B
Werkskennlinie
(Kennlinie 1)
0
1
Invertierte Kennlinie
(Kennlinie 2)
A
0
1
Kennlinie Schaltfenster
(Kennlinie 3)
B
B
0
1
A
Invertierte Kennlinie Schaltfenster
(Kennlinie 4)
Figure 4: all possible switching patterns
5.2.3.1 Examples for numerical Teach-in:
1) An “ON” threshold shall be set at 130mm distance (B) -> (characteristic 1).
Setting the switching function:
Switching- / Teach function: 0
Point A absolute in tenth of mm:
65535
FFFF hex (= Switching point A)
(Must be set to 65535 since only one switching point required)
Point B absolute in tenth of mm:
1300
0514 hex (= Switching point B)
Parameter to be written:
Switching points work:
FFFF0514 hex
2) An “OFF” threshold shall be set at 70mm distance (A) -> (characteristic 2).
Setting the switching function:
Switching- / Teach function: 0
Point A absolute in tenth of mm:
700
02BC hex (= Switching point A)
Point B absolute in tenth of mm:
65535
FFFF hex (= Switching point B)
(Must be set to 65535 since only one switching point required)
Parameter to be written:
Switching points work:
02BCFFFF hex
factory characteristic
(characteristic 1)
inverted characteristic
(characteristic 2)
Switching window characteristic
(characteristic 3)
Inverted switching window
characteristic
(characteristic 4)
Measuring distance
switching bit / switching output