Furnace is shipped from factory in upflow configuration. Pressure tube and drain tube routing MUST match the diagrams below.

Tube location when used in DOWNFLOW application

Tube location when used on

HORIZONTAL - RIGHT application

PLUG

CAP

COLLECTOR BOX DRAIN TUBE

(BLUE & WHITE STRIPED)

COLLECTOR BOX TUBE

(PINK)

COLLECTOR BOX DRAIN TUBE

(BLUE)

INDUCER HOUSING DRAIN TUBE

(VIOLET)

COLLECTOR BOX TUBE

(PINK)

COLLECTOR BOX DRAIN

TUBE

(BLUE & WHITE STRIPED)

COLLECTOR BOX DRAIN TUBE

(BLUE)

INDUCER HOUSING (MOLDED) DRAIN TUBE

(BEHIND COLLECTOR BOX DRAIN TUBE)

FIELD-INSTALLED

FACTORY-SUPPLIED DRAIN TUBE

COUPLING (LEFT DRAIN OPTION)

FIELD-INSTALLED FACTORY-SUPPLIED

DRAIN TUBE

FIELD-INSTALLED

FACTORY-SUPPLIED 1/2-IN.

CPVC STREET ELBOWS (2)

FOR LEFT DRAIN OPTION

COLLECTOR BOX TUBE

(GREEN)

CONDENSATE TRAP

CAP

Condensate Trap; Factory Installed

in Blower Shelf

CONDENSATE TRAP

COLLECTOR BOX TUBE (GREEN)

Condensate Trap on LEFT

Side Optional

CAP

PLUG

COLLECTOR BOX

DRAIN TUBE (BLUE)

PLUGGED END

COLLECTOR BOX DRAIN TUBE

(BLUE & WHITE STRIPED)

COLLECTOR BOX

TUBE (GREEN)

COLLECTOR BOX

TUBE (PINK)

COLLECTOR BOX

EXTENSION TUBE

CONDENSATE TRAP

INDUCER HOUSING DRAIN TUBE (VIOLET)

COLLECTOR BOX

EXTENSION TUBE

COLLECTOR BOX TUBE

(PINK)

COLLECTOR BOX DRAIN TUBE

(BLUE)

COLLECTOR BOX TUBE

(GREEN)

CONDENSATE TRAP

INDUCER HOUSING DRAIN

TUBE (VIOLET)

COLLECTOR BOX EXTENSION TUBE

COLLECTOR BOX DRAIN

TUBE

(BLUE & WHITE STRIPED)

Condensate Trap on

RIGHT Side

COLLECTOR BOX

EXTENSION DRAIN TUBE

DRAIN TUBE COUPLING

GAS VALVE

DRAIN TUBES ROUTED IN

FRONT OF GAS VALVE

PLUG

CAP

COLLECTOR BOX DRAIN TUBE

(BLUE & WHITE STRIPED)

CONDENSATE TRAP

COLLECTOR BOX

EXTENSION TUBE

COLLECTOR BOX

TUBE (GREEN)

INDUCER HOUSING

DRAIN TUBE

(VIOLET)

COLLECTOR BOX TUBE (PINK)

RELOCATE TUBE BETWEEN BLOWER

SHELF AND INDUCER HOUSING FOR

040,060, AND 080 HEATING INPUT

FURNACES

CAP

PLUG

COLLECTOR BOX DRAIN TUBE

(BLUE)

COLLECTOR BOX EXTENSION TUBE

COLLECTOR BOX TUBE (PINK)

COLLECTOR BOX

TUBE (GREEN)

COLLECTOR BOX DRAIN TUBE

(BLUE AND WHITE STRIPED)

INDUCER HOUSING DRAIN TUBE (VIOLET)

CONDENSATE TRAP

Condensate Trap on

LEFT Side

COLLECTOR BOX

DRAIN TUBE (BLUE)

PLUG

Tube location when used in UPFLOW application

Tube location when used on

HORIZONTAL - LEFT application

CAP

PLUG

COLLECTOR BOX

EXTENSION TUBE

DRAIN TUBE

COUPLING

COLLECTOR BOX EXTENSION DRAIN TUBE

(Blower access panel removed)

1. All tubing must be connected securely and routed to avoid kinks and traps.

2. Pressure tubing must always slope away from pressure switch to collector box connection as shown.

3. HORIZONTAL-LEFT installations require the collector box pressure tube to be relocated between the inducer housing and the blower shelf to

prevent a trap.Refer to the Installation Instructions for further details.

NOTE:

324999-201 REV. C

FIELD-INSTALLED

FACTORY-SUPPLIED

DRAIN TUBE COUPLING

(RIGHT DRAIN OPTION)

BURNER ENCLOSURE

PRESSURE REFERENCE

TUBE ASSEMBLY

BURNER ENCLOSURE

PRESSURE REFERENCE

TUBE ASSEMBLY

BURNER ENCLOSURE PRESSURE

REFERENCE TUBE ASSEMBLY

BURNER ENCLOSURE

PRESSURE REFERENCE

TUBE ASSEMBLY

BURNER ENCLOSURE

PRESSURE REFERENCE

TUBE ASSEMBLY

BURNER ENCLOSURE PRESSURE

REFERENCE TUBE ASSEMBLY

TUBE ROUTING

AUXILIARY "J" BOX RELOCATED HERE

A00308

Fig. 10 -- Furnace Pressure and Drain Tubing Diagram

8. Flush inside of collector box with water until discharge

from condensate trap is clean and runs freely.

9. Inspect inside area of collector box for any pieces of foreign

materials and remove them if present.

UNIT DAMAGE HAZARD
Failure to follow this caution may result in furnace

component damage.
DO NOT use wire brush or other sharp object to inspect or

dislodge materials in secondary heat exchangers as cutting

of the secondary heat exchanger protective coating may

occur. Flush with water only.

CAUTION

!

10. Reassemble inducer assembly by reversing items 3--7.

Tighten the vent coupling clamp screw(s) to 15 in.--lb of

torque.

NOTE: If seal between the inducer housing and the collector box
is damaged in any way, it must be repaired. To repair, apply sealant
releasing agent such as PAM cooking spray or equivalent (must not
contain corn nor canola oil, halogenated hydrocarbons nor
aromatic content, to prevent inadequate seal from occurring) to

inducer housing. (See Fig. 12.) Apply a small bead of G.E. RTV
162, G.E. RTV 6702, or Dow--Corning RTV 738 sealant to groove
in collector box.

11. Refer to furnace wiring diagram and reconnect wires to in-

ducer motor and pressure switches or connectors.

12. Reconnect pressure tubes to pressure switches. See diagram

on main furnace door for proper location of tubes. Be sure
tubes are not kinked. (See Fig. 10.)

13. Turn on gas and electrical supplies to furnace.
14. Check furnace operation through two complete heat operat-

ing cycles. Check area below inducer housing, vent pipe,
and condensate trap to ensure no condensate leaks occur. If
leaks are found, correct the problem.

15. Check for gas leaks.

FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal

injury, death or property damage.
Never test for gas leaks with an open flame. Use a

commercially available soap solution made specifically for

the detection of leaks to check all connections.

!

WARNING

58MC